2006-10-24 15:03:29***UNSAT **
  
 1) NOTE: PLEASE SEE NEW SCOPE OF WORK AND RISER
 INCLUDES NEW WORK FOR 277/480V WHICH IS REQUIRED TO BE
 DONE BY A PE.
 PLEASE SEE FS 471.003(2)(H)2A)
  
 2) NOTE: PLEASE SEE LOCATION OF THE NEW GROUNDIGN
 ELECTRODE SYSTEM FORTHE NEW SD SYSTEM IS NOT SHOWN.
 ATTACHMENT ETC. 250.66, 250.50,250.30,250.20
  
 3) NOTE: PLEASE SEE RISER SHOWS A NUETRAL CONDUCTOR
 BEING INSTALLED TO THE SD SYSTEM???
  
 4) NOTE: PLEASE SEE NO OCP SHOWN FOR NEW FEED FROM
 EXISTING KPR? 450.3. ,
 SHOWS 3KVA TRANSFORMER?
  
 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR ALL
 INCREASED AND ADDED LOADS.
  
 THESE NOTES ARE PRELIMINARYBASED ON THE RISER
 SUIBMITTED, HOWEVER ONCE PLANS SUBMITTED DONE BY AN PE,
 A REVIEW WILL COMMENCE ON THOSE SAID PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]