| Plan Review Notes For Permit 05061374 |
| Permit Number |
05061374 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-24 15:03:29 | ***UNSAT ** | | | | | | 1) NOTE: PLEASE SEE NEW SCOPE OF WORK AND RISER | | | INCLUDES NEW WORK FOR 277/480V WHICH IS REQUIRED TO BE | | | DONE BY A PE. | | | PLEASE SEE FS 471.003(2)(H)2A) | | | | | | 2) NOTE: PLEASE SEE LOCATION OF THE NEW GROUNDIGN | | | ELECTRODE SYSTEM FORTHE NEW SD SYSTEM IS NOT SHOWN. | | | ATTACHMENT ETC. 250.66, 250.50,250.30,250.20 | | | | | | 3) NOTE: PLEASE SEE RISER SHOWS A NUETRAL CONDUCTOR | | | BEING INSTALLED TO THE SD SYSTEM??? | | | | | | 4) NOTE: PLEASE SEE NO OCP SHOWN FOR NEW FEED FROM | | | EXISTING KPR? 450.3. , | | | SHOWS 3KVA TRANSFORMER? | | | | | | 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR ALL | | | INCREASED AND ADDED LOADS. | | | | | | THESE NOTES ARE PRELIMINARYBASED ON THE RISER | | | SUIBMITTED, HOWEVER ONCE PLANS SUBMITTED DONE BY AN PE, | | | A REVIEW WILL COMMENCE ON THOSE SAID PLANS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER. | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2006-10-24 14:54:13 | REVISION RECEIVED FROM FRONT COUNTER SUPREVISOR ON | | | 10/23/06 AS THIS WAS SUBMITTED IN ERROR UNDER THE WRONG | | | PERMIT NUMBER. (06082172) |
|