| Plan Review Notes For Permit 05061374 |
| Permit Number |
05061374 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-14 00:00:00 | ** UNSAT ** | | | | | | PLEASE SEE THE PLANS ARE COMNING BACK | | | DUE TO ZONING COMMENTS. PLEASE MAKE THE | | | BELOW CORRECTIONS AT THIS TIME. | | | | | | 1)NOTE: PLEASE SHOW LOAD FOR EXISTING | | | PANEL "LG". PLEASE SEE PLANS MENTIONS TO | | | REMOVE A COOLER/FREEZER CIRCUIT AND | | | INSTALL NEW 50A BRKR FOR NEWSUB-PANEL, | | | HOWEVER WHAT SIZE WAS EXISTING BRKR? WAS | | | THERE AN INCREASE IN LOAD? | | | 220,215.5 | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM EXISTING PANEL | | | TO NEW SUB PANEL. | | | 250.110,250.24,250.122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|