Plan Review Notes
Plan Review Notes For Permit 05061374
Permit Number 05061374
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061374
 ADD: 900 S OLIVE
 CONT: PURDY CONST
 TEL: (561)718-8082
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS DO NOT PROVIDE THE BUILDING
 CLASSIFICATION BY TYPE OF CONSTRUCTION.
  
 3) PLANS INDICATE A LANDING THAT HAS THE
 LANDING DECREASED BY A EXISTING
 CONCREETE CURB. 1007.4.2THE WIDTH OF
 LANDINGS SHALL BE NOT LESS
 THAN THE WIDTH OF STAIRWAYS THEY
 SERVE.
  
 4) DEPENDING ON THE RESULTS OF QUESTION
 NUMBER TWO DETAIL #2 ON S-2 MAY OR MAY
 NOT HAVE COMBUSTIBLE WALLS & ROOF
 FRAMING MEMBERS & SHEATHING. TABLE 600.
 WHY DOES THE PLYWOOD STOP SHORT OF THE
 TPO PLATE?IF LEFT THIS WAY
 FIREBLOCKING REQUIRED AT THE TOP OF
 PLYWOOD.
  
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROOFING ASSEMBLIES
 B) TRUSS STRAPS
  
 7) STAIRS TO HAVE A HANDRAIL BOTH SIDES
 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  