| 2005-07-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1. SHT A-1.0 AN RPZ BACKFLOW IS REQUIRED |
| | ON THE WATER SERVICE FOR THE TRAILERS. |
| | SHOW WATER SERVICE AND BACKFLOW ON |
| | PLANS. |
| | 2. SHT A-1.0 INDICATES A SANITARY |
| | HOLDING TANK. A PERMIT FROM THE COUNTY |
| | HEALTH DEPT. IS REQUIRED FOR THE HOLDING |
| | TANK. PLEASE CONTACT FRANK LOMBARDO |
| | (561) 233-5139. PERMIT SHALL BE |
| | SUBMITTED WITH PLANS WHEN RESUBMITTING |
| | FOR REVIEW FOR PERMIT. SECTION 104.7.1 |
| | 3. SHT A-2.0 SHOW THE CLEAR FLOOR SPACE |
| | FOR THE FOLLOWING: |
| | A. 11-4.15.5 WATER COOLER |
| | B. 11-4.16.2 WATER CLOSETS |
| | C. 11-4.19.3 LAVS |
| | 4. SHT A-3.0 RESTROOM DETAILS - SHOW THE |
| | FOLLOWING: |
| | (FOR W/C'S) |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | B. 11-4.16.6 DISPENSERS |
| | (FOR LAVS) |
| | A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | B. 11-4.19.5 FAUCETS |
| | 5. WATER COOLER SHALL BE ARI-1010 |
| | COMPLIANT. SUBMIT MANUF. SPECIFICATION |
| | SHEETS. |
| | 6. SHT M-2 WATER RISER DIAGRAM. AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | RISER. SECTION 604.9. - THERMAL |
| | EXPANSION CONTROL IS REQUIRED. SECTION |
| | 607.3.2. SHOW HOW THIS IS BEING |
| | ADDRESSED. |
| | 7. SEPARATE IRRIGATION PLANS & PERMIT IS |
| | REQUIRED. SECTION 104.3.1.1. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |