Plan Review Notes
Plan Review Notes For Permit 05061348
Permit Number 05061348
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-11 00:00:00DENIED;
 ADD TO NOTES;
 1.WATER SUPPLY LOCAL ORD. #2853-95
 BACKFLOW REQUIRED ON WATER SERVICE.
 2.ADD TO NOTE # 4 NO AIR TESTS PERMITED
 PER. MANUFACTORS RECOMMENDATIONS.
 3.PER FBC PLUMBING SEC 605.21 PURPLE
 PRIMER IS REQUIRED ON ALL PIPE AND
 FITINGS.
 4.ALL WATER HEATER EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNIONS
 CONNECTIONS ADJACENT TO HEATER.
 5.ADD NOTE TO VENT LINE DETAIL, LABLE
 VENT SAFTY DEVISE DONOT REMOVE. ALSO ADD
 TO NOTE SCREEN REQUIRED AT OPENING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695