| 2005-12-16 00:00:00 | |
| | |
| | DENIED |
| | |
| | 2ND REQUEST; |
| | |
| | 1) A RECORED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED BEFORE A PERMIT |
| | CAN BE ISSUED |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY AND THE PLANS STAMPED PRIOR |
| | TO A PERMIT BEING ISSUED. A COPY OF THE |
| | RECEIPT SHALL BE SUBMITTED TO THE CITY |
| | OF WPB CONSTRUCTION DEPT. |
| | |
| | 3) A SITE SPECIFIC SECTION OF THE STAIRS |
| | THAT COMPLY WITH THE FBC SHOWING TOTAL |
| | RISE AND RUN, ACTUAL RISER AND TREAD |
| | SIZES |
| | |
| | 4) GUARDRAIL DETAIL ON 5/10 IS NOT CODE |
| | COMPLIANT |
| | |
| | 5) ENERGY CALC'S THAT WERE SUBMITTED ARE |
| | NOT SIGNED BY OWNER/AGENT AND PAGE 600A |
| | DOES NOT MATCH SPEC'S IN DRAWINGS. |
| | EG. #10 ON 600A SPEC'S R19, DRAWING CB1 |
| | & CB2 SPEC'S R30 |
| | |
| | 6) SUBMIT 2 COPIES OF ALL PRODUCT |
| | APPROVALS MARK ALL PERTINENT INFORMATION |
| | ON THE NOA'S THAT WILL BE USED ON JOB |
| | EG. DESIGN PRESSURES,FASTENERS,SPACING |
| | ETC. |
| | |
| | 7) SHUTTER PRODUCT APPROVALS SHALL BE |
| | ACCOMPANIED BY A KEY PLAN SHOWING |
| | EMERGENCY EGRESS OPENING AND A SCHEDULE |
| | SIMILAR TO A SAMPLE THAT IS ATTACHED TO |
| | THIS NOTE |
| | |
| | 8) ANY DRAWINGS THAT ARE NOT RELEVANT |
| | SHOULD BE REMOVED FROM SUBMITTALS |
| | |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |