| 2005-07-05 00:00:00 | DENIED: |
| | 1.RETURN AIR JUMPERS SHALL BE A MINMUM |
| | OF 1 1/2 TIMES GREATER THAN THE SUPPLY |
| | AIR INTO THAT SPACE.ALL SUPPLY AIR |
| | INTO THE MASTER SUITE SHALL BE INCLUDED |
| | FOR PROPER SIZING OF THE RETURN AIR. |
| | (EXAMPLE - MASTER SUITE 1 INDICATES A |
| | 16" SUPPLY, RETURN SHALL BE A MINIMUM OF |
| | 20").2001 FBC(M)601.4 EXCEPTION 1 & 3. |
| | PLEASE SIZE ALL RETURN AIR JUMPERS |
| | ACCORDINGLY. |
| | |
| | 2.PLEASE CLARIFY THE FOLLOWING ON THE |
| | 1ST FLOOR 5 TON AHU.PROVIDE DETAIL FOR |
| | THE RETURN AIR INTO THE AHU.NO PLENUMS |
| | IN THE GARAGE AREA.INDICATE DOOR TYPE |
| | TO THE 1ST FLOOR AHU CLOSET. |
| | |
| | 3.THE "GRAND ROOM" APPEARS TO HAVE A |
| | FIRE PLACE.PLEASE CLARIFY.SHOULD |
| | FIRE PLACE BE PLANNED, PLEASE PROVIDE |
| | MANUFACTURER'S SUBMITTAL DATA & INDICATE |
| | VENTING AND AIR MAKE-UP. |
| | |
| | 4.PROVIDE ENERGY AND MANUAL J |
| | CALCULATIONS PER 2001 FBC CHAPTER 13 SUB |
| | CHAPTER 6. |
| | |
| | 5.PLANS INDICATE COMPLIANCE WITH 2001 |
| | FBC FOR 130 MPH WIND LOAD.THIS SHOULD |
| | READ 140 MPH WIND LOAD IN ACCORDANCE |
| | WITH 2001 FBC AMENDMENTS 1606.1.6. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |