Plan Review Notes
Plan Review Notes For Permit 05061297
Permit Number 05061297
Review Stop M
Sequence Number 1
Notes
Date Text
2005-07-05 00:00:00DENIED:
 1.RETURN AIR JUMPERS SHALL BE A MINMUM
 OF 1 1/2 TIMES GREATER THAN THE SUPPLY
 AIR INTO THAT SPACE.ALL SUPPLY AIR
 INTO THE MASTER SUITE SHALL BE INCLUDED
 FOR PROPER SIZING OF THE RETURN AIR.
 (EXAMPLE - MASTER SUITE 1 INDICATES A
 16" SUPPLY, RETURN SHALL BE A MINIMUM OF
 20").2001 FBC(M)601.4 EXCEPTION 1 & 3.
 PLEASE SIZE ALL RETURN AIR JUMPERS
 ACCORDINGLY.
  
 2.PLEASE CLARIFY THE FOLLOWING ON THE
 1ST FLOOR 5 TON AHU.PROVIDE DETAIL FOR
 THE RETURN AIR INTO THE AHU.NO PLENUMS
 IN THE GARAGE AREA.INDICATE DOOR TYPE
 TO THE 1ST FLOOR AHU CLOSET.
  
 3.THE "GRAND ROOM" APPEARS TO HAVE A
 FIRE PLACE.PLEASE CLARIFY.SHOULD
 FIRE PLACE BE PLANNED, PLEASE PROVIDE
 MANUFACTURER'S SUBMITTAL DATA & INDICATE
 VENTING AND AIR MAKE-UP.
  
 4.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS PER 2001 FBC CHAPTER 13 SUB
 CHAPTER 6.
  
 5.PLANS INDICATE COMPLIANCE WITH 2001
 FBC FOR 130 MPH WIND LOAD.THIS SHOULD
 READ 140 MPH WIND LOAD IN ACCORDANCE
 WITH 2001 FBC AMENDMENTS 1606.1.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  