| Plan Review Notes For Permit 05061297 |
| Permit Number |
05061297 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-24 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE LOAD CALCULATIONS AND | | | PANEL SCHEDULES PER 215.5. | | | | | | 2} INDICATE AIC RATING OF ALL SERVICE | | | EQUIPMENT PER 110.9 & 10. | | | | | | 3} SHOW GEC SYSTEM PER 250.50, SIZED PER | | | 250.66. | | | | | | 4} SHOW ALL EQUIPMENT THAT IS SERVICE | | | RELATED ON THE RISER DIAGRAM, DO NOT USE | | | A GENERIC MODEL. | | | | | | 5} THERE ARE SEVERAL LOCATIONS WHERE | | | RECEPTACLE SPACING DOES NOT MEET THE | | | REQUIREMENTS OF 210.52(A)(1),(2). SEE | | | REVIEWED PLANS . | | | | | | 6} A RECEPTACLE IS NEEDED AT THE | | | CONDENSER PER 210.63. | | | | | | 7} A RECEPTACLE MUST BE PLACED OUTSIDE | | | IN THE FRONT FOR COMPLIANCE WITH | | | 210.52(E). | | | | | | 8 A SMOKE DETECTOR AT THE STAIRS ON THE | | | FIRST FLOOR IS NEEDED PER 905.2.2 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|