Plan Review Notes
Plan Review Notes For Permit 05061297
Permit Number 05061297
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE LOAD CALCULATIONS AND
 PANEL SCHEDULES PER 215.5.
  
 2} INDICATE AIC RATING OF ALL SERVICE
 EQUIPMENT PER 110.9 & 10.
  
 3} SHOW GEC SYSTEM PER 250.50, SIZED PER
 250.66.
  
 4} SHOW ALL EQUIPMENT THAT IS SERVICE
 RELATED ON THE RISER DIAGRAM, DO NOT USE
 A GENERIC MODEL.
  
 5} THERE ARE SEVERAL LOCATIONS WHERE
 RECEPTACLE SPACING DOES NOT MEET THE
 REQUIREMENTS OF 210.52(A)(1),(2). SEE
 REVIEWED PLANS .
  
 6} A RECEPTACLE IS NEEDED AT THE
 CONDENSER PER 210.63.
  
 7} A RECEPTACLE MUST BE PLACED OUTSIDE
 IN THE FRONT FOR COMPLIANCE WITH
 210.52(E).
  
 8 A SMOKE DETECTOR AT THE STAIRS ON THE
 FIRST FLOOR IS NEEDED PER 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  