2005-07-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE PERSONAL SIGNATURE OF
 THE ARCHITECT SHALL APPEAR ON ALL
 ARCHITECTURAL DOCUMENTS. THE SEAL HAS
 BEEN STAMPED WITH THE ARCHITECTS NAME
 AND IS NOT THE REQUIRED SIGNATURE. FAC
 61G1-16.003 & FS 481.2055
 2. SHTS A-1 AND P-1 BED #3 EXISTING SINK
 BEING CAPPED OFF. IN THE REMOVAL OF ANY
 PART OF A DRAINAGE SYSTEM, DEAD ENDS ARE
 NOT APPROVED. SECTION 704.5.
 3. SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. FLOOR PLAN
 SHOWS THE BUILDING DRAIN LINE TO THE
 RIGHT SIDE OF THE FIXTURES AND THE SANT.
 RISER DIAGRAM SHOWS THE BUILDING DRAIN
 LINE TO THE LEFT SIDE OF THE FIXTURES.
 PLEASE CORRELATE FLOOR PLAN & RISER. -
 SHOW ALL PIPE SIZES. SECTION 104.2.1.
 4. SHT P-1 FIRST FLOOR PLUMBING PLAN,
 FITTINGS CONNECTING THE TOILET ROOMS AND
 THE BRANCH LINE DO NOT COMPLY WITH
 SECTION 706.3. THEY DO NOT GUIDE THE
 WASTE IN THE DIRECTION OF FLOW.
 5. SHT P-1 WATER RISER DIAGRAM, THE
 HEATER SHALL HAVE THERMAL EXPANSION
 CONTROL PER SECTION 607.3.2.
 6. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE SPACE OR BUILDING.
 SECTION 608.13.2.
 7 SHT P-1 TOILET DETAILS. SHOW THE
 FOLLOWING:
 FOR THE TOILET
 A. CLEAR FLOOR SPACE 11-4.16.2
 B. FLUSH CONTROLS 11-4.16.5
 FOR THE LAV
 A. CLEAR FLOOR SPACE.
  