| Notes |
| Date |
Text |
| 2005-07-11 00:00:00 | 1. ACCORDING TO THE PERMIT APPLICATION | | | THE PROPOSED CONSTRUCTION IS FOR A | | | SLEEP CENTER. IF PERSONS ARE EXPECTED | | | TO SLEEP INSIDE THE LOCATION, ELECTRIC | | | POWERED SMOKE DETECTORS WILL BE REQUIRED | | | THROUGHOUT THE PREMISE. | | | | | | 2. THE NOTE ON PAGE E-2 DOES NOT APPEAR | | | TO BE CORRECT. EXIT DOORS SHALL BE | | | OPENABLE FROM THE INSIDE WHEN IT IS | | | OCCUPIED. PLEASE REVIEW SPECIAL | | | LOCKING ARRANGEMENTS WITHIN THE LIFE | | | SAFETY CODE, 2003 EDITION. PLEASE VERIFY | | | COMPLIANCE WITH THE APPLICABLE CODE | | | REQUIREMENTS FOR LOCKING DEVICES. | | | | | | 3. PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 835-2910 | | | | | | |
|