| Plan Review Notes For Permit 05061295 |
| Permit Number |
05061295 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-13 00:00:00 | DENIED | | | 1)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE OCCUPANCY OF THE BUILD OUT | | | APPEARS TO BE GROUP I UNRESTRAINED PER | | | FBC 309.1. INDICATE TYPE OF OCCUPANCY ON | | | THE PLANS. CLARIFY IF PATIENTS ARE | | | MEDICATED AND LENGTH OF STAY, ETC. | | | | | | 3) FBC TABLE 500 REQUIRES THIS OCCUPANCY | | | TYPE TO HAVE AN APPROVED SPRINKLER | | | SYSTEM. SPECIFY ON THE PLANS. | | | | | | 4) SEE FBC TABLE 803.3 FOR MINIMUM | | | INTERIOR FINISH CLASSIFICATIONS. ALSO | | | SEE NOTE 1. | | | | | | 5) INSTITUTIONAL OCCUPANCIES ARE | | | REQUIRED TO HAVE A 2 HOUR FIRE | | | SEPARATION FROM OTHER OCCUPANCIES PER | | | FBC 704.1.1. | | | | | | 6) FBC TABLE 704.2.4 REQUIRES EXIT | | | ACCESS WALLS TO RESIST THE PASSAGE OF | | | SMOKE. SEPECIFY THE RATING OF THE | | | EXISTING TENANT SEPARATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | | | | |
|