Plan Review Notes
Plan Review Notes For Permit 05061295
Permit Number 05061295
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-13 00:00:00DENIED
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE OCCUPANCY OF THE BUILD OUT
 APPEARS TO BE GROUP I UNRESTRAINED PER
 FBC 309.1. INDICATE TYPE OF OCCUPANCY ON
 THE PLANS. CLARIFY IF PATIENTS ARE
 MEDICATED AND LENGTH OF STAY, ETC.
  
 3) FBC TABLE 500 REQUIRES THIS OCCUPANCY
 TYPE TO HAVE AN APPROVED SPRINKLER
 SYSTEM. SPECIFY ON THE PLANS.
  
 4) SEE FBC TABLE 803.3 FOR MINIMUM
 INTERIOR FINISH CLASSIFICATIONS. ALSO
 SEE NOTE 1.
  
 5) INSTITUTIONAL OCCUPANCIES ARE
 REQUIRED TO HAVE A 2 HOUR FIRE
 SEPARATION FROM OTHER OCCUPANCIES PER
 FBC 704.1.1.
  
 6) FBC TABLE 704.2.4 REQUIRES EXIT
 ACCESS WALLS TO RESIST THE PASSAGE OF
 SMOKE. SEPECIFY THE RATING OF THE
 EXISTING TENANT SEPARATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved