| Plan Review Notes For Permit 05061293 |
| Permit Number |
05061293 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-08 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SUBMIT THE GENERATOR AND TRANSFER | | | SWITCH MANUFACTURERS SPEC'S. HI-LITE THE | | | PRIME MOVER. | | | | | | 2} ONE SHEET INDICATES A 25K GENERATOR | | | AND THE OTHER A 30K. PLEASE CORRELATE. | | | | | | 3} SEE 445.13 FOR FEEDER SIZE. 115%. | | | | | | DISCONNECTING MEANS PER 225.30 AND | | | 225.36. INDICATE SAME, TRANSFER SWITCH | | | MAY NOT BE SERVICE RATED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|