| Date |
Text |
| 2005-06-30 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} SUBMIT TWO COPIES OF THE GENERATOR |
| | AND TRANSFER SWITCH SPECIFICATIONS. |
| | INDICATE THE PRIME MOVER, HI-LITE |
| | CORRECT ONE IF TWO ARE LISTED IN SPEC'S. |
| | |
| | 2} THE TOTAL VALUE OF THE EQUIPMENT AND |
| | LABOR MUST BE ON THE APPLICATION. IF |
| | THIS IS OBJECTIONAL TO THE CONTRACTOR, |
| | THEN THE OWNER MUST APPLY FOR A PERMIT |
| | TO SET THE GENERATOR DECLARING TOTAL |
| | VALUE AT THE SAME TIME THE OTHER |
| | REQUIRED APPLICATIONS ARE SUBMITTED, PER |
| | 104.6.5 CWPB AMMENDMENDTS. |
| | |
| | 3} PLEASE SUBMIT A SITE/FLOOR PLAN |
| | INDICATING THE PHYSICAL LOCATION OF ALL |
| | SERVICE AND GENERATOR EQUIPMENT SO |
| | COMPLIANCE WITH 225.32 AND 225.36 CAN BE |
| | REVIEWED. |
| | |
| | 4} SUBMIT LOAD CALCULATIONS FOR THE LOAD |
| | SERVED BY THE GENERATOR PER 230.31(B). |
| | SEE 702.5 INDICATING 100% OF DEMAND. |
| | THIS OFFICE WILL ACCEPT 230.31(B). 3VA |
| | FOR APPLIANCES AND GENERAL LIGHTING LOAD |
| | . |
| | |
| | 5} THE PERSON TAKING RESPONSIBILITY FOR |
| | THE PLAN MUST PRINT AND SIGN NAME ON THE |
| | PLANS. 104.2.1 FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |