Plan Review Notes
Plan Review Notes For Permit 05061271
Permit Number 05061271
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT TWO COPIES OF THE GENERATOR
 AND TRANSFER SWITCH SPECIFICATIONS.
 INDICATE THE PRIME MOVER, HI-LITE
 CORRECT ONE IF TWO ARE LISTED IN SPEC'S.
  
 2} THE TOTAL VALUE OF THE EQUIPMENT AND
 LABOR MUST BE ON THE APPLICATION. IF
 THIS IS OBJECTIONAL TO THE CONTRACTOR,
 THEN THE OWNER MUST APPLY FOR A PERMIT
 TO SET THE GENERATOR DECLARING TOTAL
 VALUE AT THE SAME TIME THE OTHER
 REQUIRED APPLICATIONS ARE SUBMITTED, PER
 104.6.5 CWPB AMMENDMENDTS.
  
 3} PLEASE SUBMIT A SITE/FLOOR PLAN
 INDICATING THE PHYSICAL LOCATION OF ALL
 SERVICE AND GENERATOR EQUIPMENT SO
 COMPLIANCE WITH 225.32 AND 225.36 CAN BE
 REVIEWED.
  
 4} SUBMIT LOAD CALCULATIONS FOR THE LOAD
 SERVED BY THE GENERATOR PER 230.31(B).
 SEE 702.5 INDICATING 100% OF DEMAND.
 THIS OFFICE WILL ACCEPT 230.31(B). 3VA
 FOR APPLIANCES AND GENERAL LIGHTING LOAD
 .
  
 5} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN NAME ON THE
 PLANS. 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved