| 2005-09-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | FROM PREVIOUS REVIEWS: |
| | 1. PLANS SHALL BE ROUTED TO DBPR HOTEL |
| | AND RESTURANT DIVISION FOR REVIEW PRIOR |
| | TO RESUBMITTING TO CITY WPB FOR REVIEW. |
| | EACH SET OF PLANS SHALL BE STAMPED BY |
| | DBPR, AND THE 2 PAGE "WORK SHEETS SHALL |
| | BE ATTACHED TO EACH SET OF PLANS. |
| | SECTION 101.4.7. - THE PLANS ARE NOT |
| | STAMPED AND THE "WORK SHEETS" ARE NOT |
| | ATTACHED TO EACH SET OF PLANS. |
| | 4. SHT P-1 WATER HEATER DETAIL, THE |
| | WATER HEATER SHALL COMPLY WITH SECTION |
| | 607.3.2 REQUIREMENT FOR THERMAL |
| | EXPANSION CONTROL. PLEASE INDICATE THE |
| | METHOD OF COMPLIANCE ON THE PLANS. THE |
| | EMERGENCY PAN FOR THE WATER HEATER |
| | REQUIRES A DRAIN LINE. PLEASE SHOW THE |
| | DRAIN LINE, SIZE PIPE, PIPE MATERIAL, |
| | AND TERMINATION POINT OF THE DRAIN LINE |
| | ON THE PLANS. SECTION 504.8.2. - PER |
| | SECTION 104.2.1. SUCH INFORMATION SHALL |
| | BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR |
| | SPECIFIC INFORMATION. PLEASE SHOW THE |
| | REQUIRED INFORMATION ON THE PLANS. |
| | ************NEW COMMENT************ |
| | 1B. PLEASE SEE ATTACHED SHEET CONCERNING |
| | THE DESIGN PROFESSIONAL AND FS |
| | 553.80(2)(B). |
| | |
| | REVIEW BY KEN STEVENS |