Plan Review Notes
Plan Review Notes For Permit 05061270
Permit Number 05061270
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
  
 1. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW PRIOR
 TO RESUBMITTING TO CITY WPB FOR REVIEW.
 EACH SET OF PLANS SHALL BE STAMPED BY
 DBPR, AND THE 2 PAGE "WORK SHEETS" SHALL
 BE ATTACHED TO EACH SET OF PLANS.
 SECTION 101.4.7
 2. GREASE INTERCEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 WASTE ORD #2938-96 OR #3434. PLEASE
 CONTACT LYNN MASSON (561) 822-2271, BY
 E-MAI [email protected], OR FAX (561)
 822-2279.
 3. SHT P-1 GREASE RISER DIAGRAM, IS
 MISLABELED AS A SANITARY RISER. SECTION
 104.2.1. ALSO THE DISH WASHER SHALL
 CONNEDT TO THE SANITARY SYSTEM, NOT THE
 GREASE SYSTEM PER UTILITY DEPT. THE DISH
 WASHER SHALL CONNECT DOWNSTREAM OF THE
 TOILET ROOM FIXTURES. SECTION 909.1.
 4. SHT P-1 WATER RISER DIAGRAM, SHOWS
 HOT & COLD TO THE ICE MACHINE, AND HOT
 AND COLD TO THE DISH WASHER. THIS DOES
 NOT REFLECT THE FOOD SERVICE EQUIPMENT
 SCHEDULE. PLEASE CLARIFY. SECTION
 104.2.1. - ALSO THE WATER HEATER SHALL
 COMPLY WITH 607.3.2 REQUIREMENT FOR
 THERMAL EXPANSION CONTROL. - ALSO THE
 P&T VALVE DISCHARGE LINE SHALL NOT HAVE
 ANY TRAPPED SECTIONS AND SHALL HAVE A
 VISIBLE AIR GAP LOCATED IN THE SAME ROOM
 AS THE HEATER. SECTION 504.7.1.
 5. SHT P-1 THE WATER RISER DIAGRAM
 INDICATES THERE IS AN EMERGENCY PAN FOR
 THE WATER HEATER. SECTION 504.8.1 A
 DRAIN LINE IS REQUIRED FOR THE PAN PER
 SECTION 504.8.2.
 6. A RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE RESTURANT. SECTION
 608.13.2.
 7. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPERATE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. - WATER HEATER IN
 CLOSET.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  