2005-07-01 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE CLARIFY / SHOW LOAD ON
 EXSITING SERVICE. IF 200A SERVICE IS
 PROVIDED, AND NO INCREASE IN LOAD,
 PLEASE SPECIFY.
 NOTE ON PLANS MENTISON "IF" IT IS
 ASSUMED??
 215.5,220
  
 2)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 3)NOTE: PLEASE CLARIFY NEW OR EXSITNG
 ROOF-TOP GFI RECEPT. 210.63,210.8
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF OLD SHEETS FOR
 REFERENCE ONLY.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  