| Plan Review Notes For Permit 05061270 |
| Permit Number |
05061270 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-01 00:00:00 | ****** UNSAT ****** | | | | | | 1)NOTE: PLEASE CLARIFY / SHOW LOAD ON | | | EXSITING SERVICE. IF 200A SERVICE IS | | | PROVIDED, AND NO INCREASE IN LOAD, | | | PLEASE SPECIFY. | | | NOTE ON PLANS MENTISON "IF" IT IS | | | ASSUMED?? | | | 215.5,220 | | | | | | 2)NOTE: PLEASE SEE 2002 NEC 210.8B3 | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | | | | 3)NOTE: PLEASE CLARIFY NEW OR EXSITNG | | | ROOF-TOP GFI RECEPT. 210.63,210.8 | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE SET OF OLD SHEETS FOR | | | REFERENCE ONLY. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|