2005-07-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT 1 IN THE INSTALLATION OR REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED. SECTION 704.5.
 ALL CAPPED OFF PIPING SHALL BE FIELD
 INSPECTED PRIOR TO COVERING.
 2. SHT 2 SUBMIT A DETAIL FOR DRINKING
 FOUNTAIN SHOWING THE FOLLOWING:
 A. SPOUT HEIGHT 11-4.15.2
 B. SPOUT LOCATION 11-4.15.3
 C. CONTROLS 11-4.15.4
 D. CLEARANCES/CLEAR FLOOR SPACE
 11-4.15.5
 E. PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. SECTION
 11-4.1.3(10)(A)
 3. SHOW THE FOLLOWING REQUIREMENTS FOR
 THE BREAK ROOM SINK:
 A. SINK DEPTH 11-4.24.4
 B. CLEAR FLOOR SPACE 11-4.24.5 FORWARD
 APPROACH REQUIRED MAXIMUM 19" UNDERNEATH
 THE SINK.
 4. SUBMIT A SANT. AND A WATER RISER
 DIAGRAM. SHOW ALL PIPE SIZES, POINTS OF
 CONNECTION, VENTS, VALVES, AND WATER
 HAMMER ARRESTORS IF REQUIRED BY SECTION
 604.9. SECTION 104.3.1.1.
  