| 2005-07-01 00:00:00 | ********* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE INDICATE NEW CIRCUITING |
| | ON PLANS AND CORRELATE WITH A PANEL |
| | SCHEDULE TO BE SUBMITTED. |
| | PLEASE SEE 700.12E FOR CIRCUTING OF |
| | EM/EXT LTS. THE BRANCH CIRCUIT FEEDING |
| | THE UNIT EQUIPMENT SHALL BE THE SAME |
| | BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | 2)NOTE: PLEASE CLARIFY IF NEW OR EXSITNG |
| | REQUIRED SIGN CIRCUIT PER 600.5 EXISTS? |
| | |
| | 3)NOTE: PLEASE SEE 210.8B3WHICH |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR |
| | TENANT SPACE(S)? |
| | APPEARS TWO TENANTS ARE BECOMING ONE. |
| | |
| | PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S)WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |