Plan Review Notes
Plan Review Notes For Permit 05061261
Permit Number 05061261
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-01 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE INDICATE NEW CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUTING OF
 EM/EXT LTS. THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 2)NOTE: PLEASE CLARIFY IF NEW OR EXSITNG
 REQUIRED SIGN CIRCUIT PER 600.5 EXISTS?
  
 3)NOTE: PLEASE SEE 210.8B3WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 TENANT SPACE(S)?
 APPEARS TWO TENANTS ARE BECOMING ONE.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S)WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717