2005-06-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061261
 ADD: 3071 CONTINENTAL DR.
 CONT: MARION CONST
 TEL: (561)662-3814
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE OPENING THAT COMMUNICATES WITHIN
 THE OLD TENANT SEPERATION WALL INDICATES
  
 A NEW 3'-0"X 6'-8" DOOR:
 1A) IS THIS TO BE (2) SEPERATE TENANTS,
 OR A SINGLE TENANT SINCE PLANS SHOW A
 20MIN RATING?
  
 1B) THIS SAME DOOR IF IT IS TO
 COMMUNICATE WITHIN A SINGLE TENANT SPACE
 SWINGS THE WRONG WAY FOR EXITING FROM
 THE TENANT SPACE,
 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE
 FOLLOWING:1012.1.2 (1). WHEN SERVING AN
 OCCUPANT LOAD OF 50 OR MORE.
  
 2) THE DOOR # 2 DOES NOT MEET EGRESS NOR
 ACCESSIBILITY REQUIREMENTS:
 2A)BUSINESS OCC. EGRESS DOOR/ 32" CLEAR:
 1004. THE WIDTH OF THE MEANS OF EGRESS
 SHALL BE DETERMINED FROM THE OCCUPANTS
 SERVED IN ACCORDANCE WITH TABLE 1004.
 2B)11-4.13.4 DOUBLE-LEAF DOORWAYS. IF
 DOORWAYS HAVE TWO INDEPENDENTLY
 OPERATED DOOR LEAVES, THEN AT LEAST
 ONE LEAF SHALL MEET THE SPECIFICATIONS
 IN 11-4.13.5 AND 11-4.13.6.THAT LEAF
 SHALL BE AN ACTIVE LEAF.
 2C) PLANS INDICATE THAT THE DOOR ALSO
 HAS A CLOSER:11-4.13.10 DOOR CLOSERS. IF
 A DOOR HAS A CLOSER, THEN THE SWEEP
 PERIODOF THE CLOSER SHALL BE ADJUSTED
 SO THAT FROM AN OPEN POSITION OF 70
 DEGREES, THE DOOR WILL TAKE AT LEAST 3
 SECONDS TO MOVE TO A POINT 3 INCHES
 (75 MM) FROM THE LATCH, MEASURED TO THE
 LEADING EDGE OF THE DOOR.
  
 2D) THIS SAME DOOR IS PART OF A EGRESS,
 BUT NO SIGNAGE FOR EXITING, 1016.1.1
 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY
 BUILDING AND STRUCTURE.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS, RAMPS, ESCALATORS,
 WALKWAYS AND EXIT PASSAGEWAYS LEADING
 TO A PUBLIC WAY.
  
  
 3) PLANS INDICATE REVERSE DOOR SWING:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  