| Plan Review Notes For Permit 05061237 |
| Permit Number |
05061237 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-07 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE NOTE THAT A EGRESS LIGHT AND | | | SWITCH MUST BE INSTALLED AT THE BATH | | | EXIT PER 210.70(A)(2)(B). | | | | | | 2} THE BATH CIRCUIT MUST COMPY WITH | | | 210.11(C)(3). MAY NOT EXTEND BEYOND THE | | | BATHROOM. INDICATE ON PLAN AND PANEL | | | SCHEDULE. | | | | | | 3} A SMOKE DETECTOR IS REQUIRED IN CLOSE | | | PROXIMETY OF THE FIRST FLOOR STAIRWELL | | | PER 905.2.2 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|