2005-08-09 00:00:00DENIED; SECOND TIME
 1.NO FUTURE STUBOUTS FOR GENERATOR.
 GENERATOR LOCATION MUST BE APPROVED BY
 ZONING AND ELECTRIC PLANS MUST BE
 SUBMITED.
 2.POOL HEATER HAS BEEN OMITED FROM
 REVISED PLAN. (POOL CONTRACTORS PERMIT
 INCLUDES THE INSTALLATION OF A GAS
 HEATER)
 3.SHOW LOCATIONS OF ALL SHUTOFF VALVES
 AND REGULATORS THAT WILL BE INSTALLED.
 4.SUBMIT CUT SHEETS FOR REGULATORS.
 5.LONGEST RUN IS STILL NOT CORRECT. (
 LOOK ON LINE DRAWING FROM METER TO WATER
 HEATER AT TOP OF THE PAGE) TOTAL OF
 169'.
 6.TOTAL BTU'S DO NOT ADD UP.
 7.WHAT IS THE BTU RATING OF THE FUTURE
 TANKLESS WATER HEATER?
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695