| 2005-06-30 00:00:00 | DENIED; | | | 1.TOTAL BTU'S IS NOT CORRECT, POOL | | | HEATER IS 400,000 BTU,S. LONGEST RUN | | | WOULD BE 133' OF PE FOR POOL HEATER. | | | FUTURE EQUIPMENT MUST BE SIZED TO MAX. | | | BTU,S SO PIPING WILL BE SIZED FOR FUTURE | | | LOAD. | | | 2.NO FUTURE STUBOUTS PERMITED FOR FUTURE | | | GENERATORS. RES. GEN. PERMIT APPLICATION | | | MUST BE SUBMITED WITH GAS PLANS AND | | | PERMIT APPLICATION. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|