Plan Review Notes
Plan Review Notes For Permit 05061207
Permit Number 05061207
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-09 00:00:00DENIED;
 1.COMPLY WITH FBC-2001 SEC. 424.2
 FBC-2001 SEC. 424.2.6.1 ENGINERRING
 2.DESIGN AND CONSTRUCTION AND WORKMAN
 SHIP. ANSI?NSPI_5. (ADD TO NOTES)+
 3.FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FBC PLUMBING. THEY WILL BE READILY
 ACCESSABLE FOR MAINT. AND REMOVAL.
 SEC.424.2.8.2 AND 424.2.8.3. PLEASE ADD
 TO NOTES.
 4.FBC 424.2.14.1 POOL HEATERS SHALL
 BEAR THE LABLE OIF A RECOGNIZED TESTING
 AGENCY. MANUFACTURES CUT SHT REQUIRED.
 MUST SHOW A POSITIVE MEANS TO RETAIN
 WATER IN HEATER.
 5.FBC SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATER EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO HEATER. ADD TO
 NOTESGAS PIPING SHALL COMPLY WITH FBC
 FUIL GAS CODE SEPARATE PLANS AND PERMIT
 REQUIRED. ADD TO NOTES.