| Plan Review Notes For Permit 05061186 |
| Permit Number |
05061186 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-30 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SUBMIT SPECIFICATIONS FOR THE | | | GENERATOR AND TRANSFER SWITCH. | | | | | | 2} SUBMIT A RISER DIAGRAM INCLUDING THE | | | NEW EQUIPMENT. SEE 225.31 AND 225.36, | | | CHECK TRANSSFER SWITCH FOR UL. | | | | | | 3} PROVIDE A CALCULATION FOR THE | | | INTENDED EMERGENCY LOAD. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|