2006-03-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061170
 ADD: 1617 N FLAGLER DR
 CONT: STEVE LUCAS AQUATICS
 TEL: (954)461-9007
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 424.1.3.1.2 POOL WET DECKS SHALL BE
 UNIFORMLY SLOPED AT A MINIMUM
 OF 2 PERCENT TO A MAXIMUM OF 4
 PERCENT AWAY FROM THE POOL OR TO DECK
 DRAINS TO PREVENT STANDING WATER.
 WHEN A CURB IS PROVIDED, THE DECK
 SHALL NOT BE MORE THAN 10 INCHES
 BELOW THE TOP OF THE CURB.
  
 THE PLANS INDICATE THE MARBLE DECK
 CONTINUEING OVER THE DECKO-DRAIN WITH A
 GEO FABRIC BELOW THE MARBLE AND ABOVE
 THE DECKO-DRAIN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026