| Plan Review Notes For Permit 05061162 |
| Permit Number |
05061162 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-18 00:00:00 | ********* UNSAT ************ | | | | | | 1)NOTE: PLEASE HAVE ENGINEER SIGN PLANS | | | WITH SIGNATURE AS ON CITY SIGNATURE FILE | | | PER FS 471.025 | | | | | | 2)NOTE: PLEASE CLARIFY METER, AS IT | | | SEEMS IT MAY BE A METER/MAIN COMBO PANEL | | | DUE TO THE NUMBER OF CONDUCTORS SHOWN. | | | IF THIS IS ONLY A METER, PLEASE COMPLETE | | | PAHSE CONDUCTORS, AND NEUTRALS TO THE | | | FIRST MEANS OF DISCONNECT. PLEASE KNOW, | | | NO "EQUIPMENT GROUNDING CONDUCTORS" ARE | | | INSTALLED BEFORE THR FIRST MEANS OF | | | DISCONNECT. PER 250.6,250.24 | | | EVEN IF THE ONLY LOADS BEING SERVED ARE | | | MOTOR LOADS, A NEUTRAL MUST BE RBOUGHT O | | | THE FIRST MEANS. | | | IF INDEED THIS IS A METER/MAIN PANEL, | | | PLEASE PROVIDE OCP FOR EACH FEEDER. | | | 240.4,310.16 ETC | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|