2006-03-18 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE HAVE ENGINEER SIGN PLANS
 WITH SIGNATURE AS ON CITY SIGNATURE FILE
 PER FS 471.025
  
 2)NOTE: PLEASE CLARIFY METER, AS IT
 SEEMS IT MAY BE A METER/MAIN COMBO PANEL
 DUE TO THE NUMBER OF CONDUCTORS SHOWN.
 IF THIS IS ONLY A METER, PLEASE COMPLETE
 PAHSE CONDUCTORS, AND NEUTRALS TO THE
 FIRST MEANS OF DISCONNECT. PLEASE KNOW,
 NO "EQUIPMENT GROUNDING CONDUCTORS" ARE
 INSTALLED BEFORE THR FIRST MEANS OF
 DISCONNECT. PER 250.6,250.24
 EVEN IF THE ONLY LOADS BEING SERVED ARE
 MOTOR LOADS, A NEUTRAL MUST BE RBOUGHT O
 THE FIRST MEANS.
 IF INDEED THIS IS A METER/MAIN PANEL,
 PLEASE PROVIDE OCP FOR EACH FEEDER.
 240.4,310.16 ETC
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  