| 2005-07-26 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)YOU ARE USING ENGINEERING TO |
| | DETERMINE WIND PRESSURES.ORIGINALS |
| | REQUIRED, FAC61G15-23.002. |
| | |
| | 2.)THE DADE COUNTY NOAS SUBMITTED WERE |
| | ILLEGIBLE.I HAVE PRINTED NEW ONES FOR |
| | YOU BUT IN THE FUTURE PLEASE PROVIDE |
| | LEGIBLE COPIES, WWW.MIAMIDADE.GOV. |
| | (BUILDING CODE COMPLIANCE, PRODUCT |
| | CONTROL) |
| | |
| | 3.)SEE PREVIOUS LISTS.FLORIDA STATE |
| | OR LOCAL PRODUCT APPROVAL REQUIRED IN |
| | ADDITION TO THE NOA PROVIDED. I HAVE |
| | PRINTED THIS FOR YOU BUT IN THE FUTURE |
| | PLEASE PROVIDE THIS AS WELL. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 4.)PROVIDE MULLION PRODUCT APPROVALS |
| | (EVALUATION REPORT AS WELL AS STATE OR |
| | LOCAL PRODUCT APPROVAL). |
| | |
| | 5.)THREE DIFFERENT PRODUCTS WERE |
| | SUBMITTED.PLEASE SUBMIT ONLY THE |
| | PRODUCT YOU WISH TO INSTALL AND CIRCLE |
| | METHOD OF ATTACHMENT IF DIFFERENT |
| | OPTIONS ARE AVAILABLE SO THAT CODE |
| | COMPLIANCE CAN BE DETERMINED.FOR |
| | INSTANCE, ON THE YALE OGREN NOA, SHEET |
| | 2, NOT ALL OPTIONS ARE COMPLIANT WITH |
| | THIS WIND PRESSURE. |
| | |
| | 6.)THE ENGINEERING IS TO HAVE A TITLE |
| | BLOCK CONTAINING ALL INFORMATION |
| | REQUIRED BY FAC61G15-23.002.A |
| | CERTIFICATE OF AUTHORIZATION NUMBER |
| | PRINTED ON THE PLAN IS REQUIRED FOR THE |
| | ERNING CORPORATION. |