| 2005-09-03 00:00:00 | *********** UNSAT ************** |
| | |
| | PLEASE KNOW THAT PLANS ARE ONLY |
| | SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT |
| | BEEN SUBMITTED FOR PERMIT AS OF YET. |
| | PLEASE ALSO KNOW, THE STATE OF FLORIDA |
| | IS SET TO CHANGE CODES ON OCT 1ST 2005. |
| | IF PLANS HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT AND FEES PAID BEFORE THAT TIME, |
| | ALL DESIGNS WILL BE REQUIRED UNDER THE |
| | NEW FBC 2004 FBCADOPTED CODES. |
| | |
| | 1)NOTE: PLEASE SHOW THE ATTACHMENT FOR |
| | NEW TRANSFORMER SHOWN. |
| | PLEASE SEE 250.30,250.66.TRANSFORMER |
| | IS NOT SHOWNATTACHED TO GROUNDING |
| | DETAIL SHOWN ON PLANS? |
| | |
| | 2)NOTE:PLEASE SEE PANEL SCHEDULE FOR HA |
| | PANEL IS SHOWING "SPARE" FOR WHAT APPEAR |
| | TO BE RTU'S/ A/C EQUIPMENT? |
| | PLEASE ALSO SEE LOAD CALCULATIONS |
| | INDICATE "0" FOR LARGEST MOTOR LOAD(S). |
| | MIN 125%, SHALL BE FIGURED. |
| | 215.3 |
| | |
| | 3)NOTE: PLEASE SEE NEW 600A MAIN |
| | INDICATES A NEW GROUNDING ELECTRODE |
| | CONDUCTOR WITH ATTACHMENT TO NEW |
| | GROUNDING ELECTRODE??? |
| | PLEASE CLARIFY. |
| | PLEASE SEE PREVIOUS NOTES WHICH |
| | REQUESTED INFORMATION WHETHER |
| | "LANDLORDS" WIREWAY CONTAINED A "MAIN" |
| | AHEAD OF WIREWAY? |
| | PLEASE SEE IF NOT THEN AN "EQIPMENT |
| | GROUNDING CONDUCTOR" WOULD ONLY BE |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT.(NEW 600A MAIN) PLEASE SEE |
| | RISER SHOWS AN EQUIPMENT GROUNDING |
| | CONDUCTOR FROM WIREWAY TO NEW 600A MAIN. |
| | THIS IS OK IF THERE IS A MAIN ON THE |
| | LINE-SIDE OF THE WIREWAY SHOWN. |
| | PLEASE SEE 250.24, AND 250.6. |
| | PLEASE BE SURE NEUTRAL "IS NOT" |
| | PARALLED. |
| | |
| | 4)NOTE: PLEASE SEE LOAD SHOWN ON PANEL |
| | "A" IS SHOWN AT 198A'S AFTER DEMANDS |
| | TAKEN. PLEASE SEE 75KVA TRANSFORMER |
| | @208V ON SECONDARY SIDE IS ONLY RATED AT |
| | 208A'S MAX. |
| | PLEASE SEE 90.7, WHICH STATES ANY DESIGN |
| | IN AN ELECTRICAL SYSTEM SHOULD PROVIDE |
| | ROOM FOR "FUTURE PLANNING" OF POSSIBLE |
| | EXPANSION OF ELECTRICAL. |
| | |
| | 5)NOTE: PLEASE CORRELATE ROOF TOP |
| | EQUIPMENT EF-1 AND MUA-1 WITH PANEL |
| | SCHEDULES, EF-1 COULD NOT BE LOCATED, |
| | ONLY EF-2? (MISPRINT)? |
| | PLEASE CORRELATE WITH MECHANICAL PLANS. |
| | MUA-1 COULD NOT BE LOCATED ON A PANEL |
| | SCHEDULE. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING> |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SEE ANY POSSIBEL COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |