Plan Review Notes
Plan Review Notes For Permit 05061023
Permit Number 05061023
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061023
 ADD: 700 S ROSEMARY # 140
 CONT:"PLAN REVIEW"
 NO CONTACT
 TEL:NO CONTACT
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) COMMENT# 4 FROM THE PREVIOUS REVIEW,
 TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 2)COMMENT# 5 FROM THE PREVIOUS REVIEW,
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) COMMENT# 6 FROM THE PREVIOUS REVIEW,
 SHEET T-1 BUILDING DESCRIPTION INDICATES
 THIS IS A TYPE V-UNPROTECTED BUILDING.
 THIS IS INCORRECT THIS IS A TYPE II
 BUILDING, FULLY SPRINKLERED.