| 2005-07-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. THE PERSONAL SIGNATURE IS REQUIRED ON |
| | ALL ARCHITECTURAL SHEETS. IT APPEARS |
| | THAT THE SHEETS ARE INITIALED AND NOT A |
| | SIGNATURE. PLEASE PROVIDE A SIGNED, |
| | SEALED, DATED AND NOTORIZED LETTER |
| | INDICATING THE LEGAL SIGNATURE OF THE |
| | ARCHITECT OF RECORD FOR OUR FILES. FAC |
| | 61G1-16.003 AND FS 481.2055. |
| | 2. THE FOLLOWING INFORMATION IS REQUIRED |
| | IN THE TITLE BLOCK OF THE ARCHITECT PER |
| | FAC 61G1-16.004(1) THRU (6): FIRM NAME, |
| | ADDRESS, & TELEPHONE NUMBER(1), FIRM |
| | LICENSE NUMBER(2), & SPACE FOR PRINTED |
| | NAME OF THE PERSON SEALING THE |
| | DOCUMENT(6). FS 481.2055. |
| | 3. A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME AS HE/SHE AFFIXES THE DATED |
| | SEAL. PER FBPE RULING INITIALS ARE NOT |
| | APPROVED. SUBMIT A SIGNED, SEALED, DATED |
| | AND NOTORIZED LETTER INDICATING THE |
| | LEGAL SIGNATURE OF THE ENGINEER OF |
| | RECORD FOR OUR RECORDS. FAC |
| | 61G15-23.002(1) AND FS 471.025 |
| | 4. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS AND LICENSE NUMBER |
| | ON EACH SHEET. IF PRACTICING THROUGH A |
| | DULY AUTHROIZED ENGINEERING BUSINESS, |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME AND LICENSE NUMBER, AS WELL AS, THE |
| | NAME, ADDRESS, AND CERTIFICATE OF |
| | AUTHROIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2) AND FS 471.025. |
| | 5. PLANS SHALL BE ROUTED TO DBPR HOTEL |
| | AND RESTURANT DIVISION FOR REVIEW. PLANS |
| | SHALL BE STAMPED AND THE 2 PAGE |
| | "WORKSHEET" ATTACHED TO EACH SET OF |
| | PLANS RESUBMITTED FOR BY CITY OF WPB. |
| | SECTION 101.4.7. |
| | 6. INDICATE IF THE RESTURANT WILL HAVE |
| | FIXED SEATING OR BE WITHOUT FIXED |
| | SEATING. SEE TABLE 1003.1. |
| | 7. SHT A1.1 TOILET ROOMS, IN NEW |
| | CONSTRUCTION A LAVATORY SHALL BE |
| | PROVIDED WITHIN THE ACCESSIBLE TOILET |
| | STALL. SEE FIG 30E. |
| | 8. SHT T1 INDICATES MAXIMUM SEATING TO |
| | BE 76, BUT SHT A1.1 INDICATES SEAT COUNT |
| | TO BE UP TO 104 ON THE SEATING SUMMARY. |
| | ALSO THE COUNT OF THE SEATS ON SHT A1.1 |
| | ADD UP TO 96. PLEASE CLARIFY AS THIS |
| | WILL AFFECT THE NUMBER OF FACILITITES |
| | REQUIRED IN TABLES 1003.1 & 403.1. |
| | SECTION 104.2.1. |
| | 9. SHT A1.1 PLEASE SUBMIT AN EQUIPMENT |
| | SCHEDULE IDENTIFYING ALL EQUIPMENT, |
| | INDICATING ALL SUPPLY AND DRAINAGE PIPE |
| | SIZES ECT. |
| | 10. SHT A1.4 RESPONSIBLIITY SCHEDULE IS |
| | INCOMPLETE. SECTION 104.2.1. |
| | 11. SHT A4.0 WHERE DOES IT INDICATE THE |
| | WALL DESIGINATION, (A-B-C-D), SO THE |
| | FINISH CAN BE MATCHED UP TO THE WALL? |
| | ALSO PLEASE SHOW HOW THE WOOD BASE AND |
| | THE WALL FINISH COMPLIES WITH SECTION |
| | 1204.2 FOR PUBLIC TOILETS. |
| | 12. AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE RESTURANT. SECTION |
| | 608.13.2. |
| | 13. SHT P1.0 PLUMBING NOTES #22 FILTER |
| | TO ICE MACHINE FILTER SHALL COMPLY WITH |
| | NSF 42. SUBMIT MANUF. SPECIFICATION |
| | SHEETS. SECTION 611.1 |
| | 14. SHT P1.0 DEMOLITION GENERAL NOTES #4 |
| | IN THE REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | SECTION 704.5. |
| | 15. SHT P1.1 OVERWALL SANITARY PLAN, THE |
| | GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| | ENVIRONMENTAL COMPLIANCE MANAGER. WASTE |
| | ORDINANCE#2938-96. CONTACT LYNN MASSON |
| | (561) 822-2271 - FAX (561) 822-2279 - |
| | E-MAIL [email protected]. PLEASE SUBMIT A |
| | COPY OF THE DETERMINATION SHEET WITH |
| | PLANS WHEN RESUBMITTING. |
| | 16. SHT P2.1 SANT. RISER DIAGRAM AND |
| | SANT. FLOOR PLAN. EVERY DRY VENT |
| | CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE |
| | HORIZONTAL DRAIN PIPI. SECTION 905.3. |
| | VENT SHALL RISE VERTICALLY TO A MINIMUM |
| | OF 6" ABOVE THE FLOOD LEVEL RIM OF THE |
| | HIGHEST TRAP OR TRAPPED FIXTURE SERVED. |
| | SECTION 905.4. |
| | 17. SHT P2.1 GREASE WASTE RISER AND |
| | GREASE FLOOR PLAN. DISHWASHERS SHALL |
| | CONNECT TO THE SANITARY SYSTEM NOT THE |
| | GREASE SYSTEM PER UTILITY DEPT. |
| | 18. SHT P2.1 GREASE WASTE RISER AND |
| | GREASE FLOOR PLAN. KEY NOTES #3 STATES |
| | "3 INCH GW TO VENTED 3" FS SEE P1.1-01 |
| | FOR CONTINUATION". THE CONTINUATION HAS |
| | NOT BEEN FOUND ON SHT P1.1-01. PLEASE |
| | CLARIFY.SECTION 104.2.1. |
| | 19. SHT P3.1 WATER RISER DIAGRAM WATER |
| | HAMMER ARRESTORS ARE REQUIRED AT THE ICE |
| | MAKER, AND THE DISH WASHERS PER SECTION |
| | 604.9. ALL WATER HAMMER ARRESTORS SHALL |
| | BE LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING. |
| | PDI-WH 201. |
| | 20. SHT P3.1 WATER RISER ISOMETRIC DOES |
| | NOT REFLECT THE FLOOR PLAN AT EQUIPMENT |
| | NUMBER 9. A CW LINE ON THE FLOOR PLAN IS |
| | NOT SHOWN ON THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 21. SHT P3.1 DETAIL P3.1-03 IS |
| | MISLABELED AS SANITARY AND VENT |
| | ISOMETRIC PLAN. THIS IS A WATER |
| | ISOMETRIC. SECTION 104.2.1. |
| | 22. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. WELDED PIPE REQUIRES A PICTURE |
| | IDENTIFICATION, WELDING CERTIFICATION, |
| | AND WELDING PROCEDURE AT TIME OF |
| | APPLICATION FOR GAS PERMIT. |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |