Plan Review Notes
Plan Review Notes For Permit 05061023
Permit Number 05061023
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE PERSONAL SIGNATURE IS REQUIRED ON
 ALL ARCHITECTURAL SHEETS. IT APPEARS
 THAT THE SHEETS ARE INITIALED AND NOT A
 SIGNATURE. PLEASE PROVIDE A SIGNED,
 SEALED, DATED AND NOTORIZED LETTER
 INDICATING THE LEGAL SIGNATURE OF THE
 ARCHITECT OF RECORD FOR OUR FILES. FAC
 61G1-16.003 AND FS 481.2055.
 2. THE FOLLOWING INFORMATION IS REQUIRED
 IN THE TITLE BLOCK OF THE ARCHITECT PER
 FAC 61G1-16.004(1) THRU (6): FIRM NAME,
 ADDRESS, & TELEPHONE NUMBER(1), FIRM
 LICENSE NUMBER(2), & SPACE FOR PRINTED
 NAME OF THE PERSON SEALING THE
 DOCUMENT(6). FS 481.2055.
 3. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AS HE/SHE AFFIXES THE DATED
 SEAL. PER FBPE RULING INITIALS ARE NOT
 APPROVED. SUBMIT A SIGNED, SEALED, DATED
 AND NOTORIZED LETTER INDICATING THE
 LEGAL SIGNATURE OF THE ENGINEER OF
 RECORD FOR OUR RECORDS. FAC
 61G15-23.002(1) AND FS 471.025
 4. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THROUGH A
 DULY AUTHROIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHROIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) AND FS 471.025.
 5. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW. PLANS
 SHALL BE STAMPED AND THE 2 PAGE
 "WORKSHEET" ATTACHED TO EACH SET OF
 PLANS RESUBMITTED FOR BY CITY OF WPB.
 SECTION 101.4.7.
 6. INDICATE IF THE RESTURANT WILL HAVE
 FIXED SEATING OR BE WITHOUT FIXED
 SEATING. SEE TABLE 1003.1.
 7. SHT A1.1 TOILET ROOMS, IN NEW
 CONSTRUCTION A LAVATORY SHALL BE
 PROVIDED WITHIN THE ACCESSIBLE TOILET
 STALL. SEE FIG 30E.
 8. SHT T1 INDICATES MAXIMUM SEATING TO
 BE 76, BUT SHT A1.1 INDICATES SEAT COUNT
 TO BE UP TO 104 ON THE SEATING SUMMARY.
 ALSO THE COUNT OF THE SEATS ON SHT A1.1
 ADD UP TO 96. PLEASE CLARIFY AS THIS
 WILL AFFECT THE NUMBER OF FACILITITES
 REQUIRED IN TABLES 1003.1 & 403.1.
 SECTION 104.2.1.
 9. SHT A1.1 PLEASE SUBMIT AN EQUIPMENT
 SCHEDULE IDENTIFYING ALL EQUIPMENT,
 INDICATING ALL SUPPLY AND DRAINAGE PIPE
 SIZES ECT.
 10. SHT A1.4 RESPONSIBLIITY SCHEDULE IS
 INCOMPLETE. SECTION 104.2.1.
 11. SHT A4.0 WHERE DOES IT INDICATE THE
 WALL DESIGINATION, (A-B-C-D), SO THE
 FINISH CAN BE MATCHED UP TO THE WALL?
 ALSO PLEASE SHOW HOW THE WOOD BASE AND
 THE WALL FINISH COMPLIES WITH SECTION
 1204.2 FOR PUBLIC TOILETS.
 12. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE RESTURANT. SECTION
 608.13.2.
 13. SHT P1.0 PLUMBING NOTES #22 FILTER
 TO ICE MACHINE FILTER SHALL COMPLY WITH
 NSF 42. SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 611.1
 14. SHT P1.0 DEMOLITION GENERAL NOTES #4
 IN THE REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5.
 15. SHT P1.1 OVERWALL SANITARY PLAN, THE
 GREASE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. WASTE
 ORDINANCE#2938-96. CONTACT LYNN MASSON
 (561) 822-2271 - FAX (561) 822-2279 -
 E-MAIL [email protected]. PLEASE SUBMIT A
 COPY OF THE DETERMINATION SHEET WITH
 PLANS WHEN RESUBMITTING.
 16. SHT P2.1 SANT. RISER DIAGRAM AND
 SANT. FLOOR PLAN. EVERY DRY VENT
 CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE
 HORIZONTAL DRAIN PIPI. SECTION 905.3.
 VENT SHALL RISE VERTICALLY TO A MINIMUM
 OF 6" ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE SERVED.
 SECTION 905.4.
 17. SHT P2.1 GREASE WASTE RISER AND
 GREASE FLOOR PLAN. DISHWASHERS SHALL
 CONNECT TO THE SANITARY SYSTEM NOT THE
 GREASE SYSTEM PER UTILITY DEPT.
 18. SHT P2.1 GREASE WASTE RISER AND
 GREASE FLOOR PLAN. KEY NOTES #3 STATES
 "3 INCH GW TO VENTED 3" FS SEE P1.1-01
 FOR CONTINUATION". THE CONTINUATION HAS
 NOT BEEN FOUND ON SHT P1.1-01. PLEASE
 CLARIFY.SECTION 104.2.1.
 19. SHT P3.1 WATER RISER DIAGRAM WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE ICE
 MAKER, AND THE DISH WASHERS PER SECTION
 604.9. ALL WATER HAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201.
 20. SHT P3.1 WATER RISER ISOMETRIC DOES
 NOT REFLECT THE FLOOR PLAN AT EQUIPMENT
 NUMBER 9. A CW LINE ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM. SECTION
 104.2.1.
 21. SHT P3.1 DETAIL P3.1-03 IS
 MISLABELED AS SANITARY AND VENT
 ISOMETRIC PLAN. THIS IS A WATER
 ISOMETRIC. SECTION 104.2.1.
 22. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. WELDED PIPE REQUIRES A PICTURE
 IDENTIFICATION, WELDING CERTIFICATION,
 AND WELDING PROCEDURE AT TIME OF
 APPLICATION FOR GAS PERMIT.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]