| Plan Review Notes For Permit 05061023 |
| Permit Number |
05061023 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-16 00:00:00 | PLAN DENIED | | | 1) PLEASE REFER TO SECTION 104.2.1 FBC. | | | DRAWINGS AND SPECIFICATIONS | | | REQUIREMENTS. | | | 2) PLEASE REFER TO SECTION 601.4 FBC(M) | | | BALANCED RETURN AIR. | | | 3) PLEASE PROVIDE FRESH AIR CALCULATIONS | | | PER TABLE 403.3 FBC(M). | | | (4 ADDITINOAL PERMITS ARE REQUIRED FOR | | | HOOD,HOOD SUPRESSION AND WALK IN | | | COOLERS. | | | 5) PLEASE REFER TO SECTION 506.3.14.2 | | | AND NFPA 96 SECTION 7.8.3 COMMERCIAL | | | HOODS WALL TERMINATIONS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|