| Plan Review Notes For Permit 05061023 |
| Permit Number |
05061023 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-27 00:00:00 | ******DENIED****** | | | | | | 1) LIFE SAFETY TO COMPLY WITH NFPA 101, | | | 2003 EDITION. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 3) PLEASE SEE OTHER REVIEW COMMENTS IN | | | REGARDS TO FS AND FAC TITLE BLOCK | | | REQUIREMENTS FOR ALL SHEETS. | | | | | | 4) PLEASE ILLUSTRATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS, | | | IE. CLASS A,B OR C. | | | | | | 5) IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS, DUCT SMOKE DETECTORS WHERE | | | PROVIDED SHALL BE WIRED TO THE FIRE | | | ALARM SYSTEM TO CAUSE A GENERAL FIRE | | | ALARM CONDITION WHEN ACTIVATED. | | | | | | 6) AN ADDRESS SUITE NUMBER IS REQUIRED | | | ON THE BUILDING. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | PLAN REVIEW(561) 805-6722 | | | WPBFR(561) 804-4756 |
|