Plan Review Notes
Plan Review Notes For Permit 05061023
Permit Number 05061023
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-05 00:00:00********* UNSAT *************
  
 ** PLAN REVIEW ONLY **
 NOT SUBMITTED FOR PERMIT.
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS PER FAC
 61G1-16.004,61G15-23.002, FS 481.219,
 471.023.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENTS ARE
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE FS 481.221, 471.025
 WHICH REQUIRES PLANS TO BE SIGNED BY
 ARCH/ ENG. PLEASE SEE PLANS APPEAR TO BE
 "SIGNED" WITH INITIALS? IF THIS IS
 INDEED THE LEGAL SIGNATURE, PLEASE
 PROVIDE A SIGNED, SEALED, DATED LTR FOR
 VERIFICATION OF LEGAL SIGNATURE. THIS
 LTR IS REQUIRD TO BE NOTORIZED UNDER THE
 GUIDELINES OF FS 117.
 THIS WILL BE PLACED IN SIGNATURE FILE
 FOR FUTURE REFERENCE.
  
 3)NOTE: PLEASE CLARIFY IF EXISITNG MAIN
 SHOWN IS THE FIRST MEANS OF DISCONNECT
 FOR SERVICE. IF SO, PLEASE SEE
 250.6,250.24 FOR EQUIPMENT GROUNDING
 CONDUCTOR SHOWN BEFORE THE FIRST MEANS
 OF DISC.
  
 4)NOTE: PLEASE SHOW THE GROUNDING
 ATTACHMENT FOR TRANSFORMER. 250.30
  
 5)NOTE: PLEASE SEE 700.12E FOR CIRCUTING
 OF EM/EXT LTS.THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE ALSO SEE 220.12 FOR TRACK LT
 LOADS TO BE SHOWN.
  
 7)NOTE: PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  