| 2005-07-05 00:00:00 | ********* UNSAT ************* |
| | |
| | ** PLAN REVIEW ONLY ** |
| | NOT SUBMITTED FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCKS PER FAC |
| | 61G1-16.004,61G15-23.002, FS 481.219, |
| | 471.023. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENTS ARE |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE FS 481.221, 471.025 |
| | WHICH REQUIRES PLANS TO BE SIGNED BY |
| | ARCH/ ENG. PLEASE SEE PLANS APPEAR TO BE |
| | "SIGNED" WITH INITIALS? IF THIS IS |
| | INDEED THE LEGAL SIGNATURE, PLEASE |
| | PROVIDE A SIGNED, SEALED, DATED LTR FOR |
| | VERIFICATION OF LEGAL SIGNATURE. THIS |
| | LTR IS REQUIRD TO BE NOTORIZED UNDER THE |
| | GUIDELINES OF FS 117. |
| | THIS WILL BE PLACED IN SIGNATURE FILE |
| | FOR FUTURE REFERENCE. |
| | |
| | 3)NOTE: PLEASE CLARIFY IF EXISITNG MAIN |
| | SHOWN IS THE FIRST MEANS OF DISCONNECT |
| | FOR SERVICE. IF SO, PLEASE SEE |
| | 250.6,250.24 FOR EQUIPMENT GROUNDING |
| | CONDUCTOR SHOWN BEFORE THE FIRST MEANS |
| | OF DISC. |
| | |
| | 4)NOTE: PLEASE SHOW THE GROUNDING |
| | ATTACHMENT FOR TRANSFORMER. 250.30 |
| | |
| | 5)NOTE: PLEASE SEE 700.12E FOR CIRCUTING |
| | OF EM/EXT LTS.THE BRANCH CIRCUIT FEEDING |
| | THE UNIT EQUIPMENT SHALL BE THE SAME |
| | BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | 6)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE ALSO SEE 220.12 FOR TRACK LT |
| | LOADS TO BE SHOWN. |
| | |
| | 7)NOTE: PLEASE BE SURE TO REMOVE ANY |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |