| Plan Review Notes For Permit 05061017 |
| Permit Number |
05061017 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-11-21 00:00:00 | PROVISO: | | | 1. PLAN SHEET M-1 PER 2001 FBC(M)501.3, | | | EXHAUST SHALL TERMINATE AT A LOCATION AS | | | NOT TO BE READILY DRAWN IN BY THE | | | VENTILATING SYSTEM.EXHAUST TERMINATION | | | APPEAR TO TERMINATE UNDERNEATH THE FRESH | | | AIR INTAKE TO AHU-1.PLEASE REVISE | | | PLANS PRIOR TO INSPECTION. | | | | | | 2. FAN SHUTDOWN REQUIRED FOR AHU-1 PER | | | 2001 FBC(M)606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|