| Plan Review Notes For Permit 05061017 |
| Permit Number |
05061017 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-03 00:00:00 | ********* NOTES REDLINED ********* | | | | | | 1)NOTE: PLEASE SEE PREVIOUS REVIEW, | | | PLANS WERE REDLINED FOR 2002 NEC 210.8B3 | | | WHICH REQUIRES ALL 15A& 20A RECEPTS IN | | | KITCHEN/LUNCH RM AREA TO BE GFI OR GFI | | | PROTECTED CIRCUITS. | | | | | | THIS WAS RED LINED PLANS ONCE AGAIN. | | | PLEASE KNOW, IF PLANS COME BACK DURING | | | CONTRUCTION FOR ANY OTHER REVISIONS, | | | PLEASE MAKE CORRECTIONS. | | | | | | NEW SHEETS E-1 AND E-2 SUBMITTED. |
|