| | BUILDING PLAN REVIEW |
| | PERMIT: 05061001 |
| | ADD: 626 CLEAR LAKE |
| | CONT: O/B HOWARD CHRISTINE |
| | TEL: (561)833-8749 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 1) FBC 104.2.1ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN.PLEASE COMPLY. |
| | |
| | 2) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 3) S-1 IS VERY VAUGEIN DESCRIBING THE |
| | FOUNDATION SIZE , CALLING IT A 10X 20 |
| | CONCRETE SLAB.1804.1.3 THE BOTTOM OF |
| | THE FOUNDATION SHALL EXTEND NO LESS THAN |
| | 12" BELOW FINISH GRADE. |
| | |
| | 4) PLANS ARE VAUGE AS TO HURRICANE |
| | STRAPPING, THEY DO NOT INDICATE LOADS TO |
| | BE RESISTED. IN SOME CASES STRAPS DO NOT |
| | |
| | PROVIDE WHAT MODEL. THEY DO NOT PROVIDE |
| | A CONTINIOUS PATH AS ILLUSTRATED. |
| | 1606.1.3 ANCHORAGE AGAINST OVERTURNING, |
| | UPLIFT AND SLIDING. STRUCTURALMEMBERS |
| | AND SYSTEMS, AND COMPONENTS AND CLADDING |
| | IN A BUILDING ORSTRUCTURE SHALL BE |
| | ANCHORED TO RESIST WIND-INDUCED |
| | OVERTURNING, UPLIFT AND SLIDING AND TO |
| | PROVIDE CONTINUOUS LOAD PATHS FOR THESE |
| | FORCES TO THE FOUNDATION.WHERE A |
| | PORTION OF THE RESISTANCE TO THESE |
| | FORCES IS PROVIDED BY DEAD LOAD, THE |
| | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE |
| | DURING A DESIGN WIND EVENT SHALL BE |
| | USED. |
| | 5)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) HURRICANE STRAPS |
| | B) ROOFING ASSEMBLIES |
| | |
| | 7) S-1 INDICATES TAP-CONS TO BE USED TO |
| | FASTEN A TOP PLATE TO THE BEAM NO SIZE |
| | OF TAP CON NOR SPACING, NOR LOADS TO BE |
| | RESISTED? |
| | |
| | 8) PLANS DO NOT INDICATE WHAT TYPE OF |
| | WIRE LATH, NOR GAUGE? PROVIDE NAILING |
| | FOR VERTICAL AND HORIZONTAL APPLICATION? |
| | |
| | 9) PLANS SHOW ELECTRICAL IN PLANS WILL |
| | REQUIE A SEPERATE PLAN WITH ASSOCIATED |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |