| Plan Review Notes For Permit 05060925 |
| Permit Number |
05060925 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-22 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE RISER SHOWS PANELS WITH MAIN | | | BREAKERS, PLAN SHOWS MAIN DISCONNECTS | | | OUTSIDE AND PANELS INSIDE. PLEASE | | | CLARIFY. | | | | | | 2} PANEL "C" IS FED FROM PANEL "B" ON | | | THE RISER, BUT OUT OF PANEL "A"ON THE | | | SCHEDULE. | | | | | | 3} INDICATE THE AIC RATING OF THE | | | SERVICE EQUIPMENT PER 110.9 & 10. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|