| 2006-05-31 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | COMMENTS FROM TWO PREVIOUS REVIEWS: |
| | |
| | COMMENTS FROM PREVIOUS REVIEW: |
| | |
| | |
| | 4. SUBMIT A WATER AND A SANITARY RISER |
| | DIAGRAM IN ISOMETRIC FORM. THE WATER |
| | RISER DIAGRAM SHALL SHOW ALL PIPE SIZES, |
| | VALVES, AND, IF REQUIRED BY SECTION |
| | 604.9, WATER HAMMER ARRESTORS. - THE |
| | SANT. RISER DIAGRAM SHALL SHOW ALL PIPE |
| | SIZES, VENTS, TRAPS AND POINT OF |
| | CONNECTION. SECTION 104.3.1.1. - NO |
| | WATER RISER ISOMETRIC SUBMITTED. TWO |
| | SANITARY RISER ISOMETRICS SUBMITTED, BUT |
| | NETHER RISER DIAGRAM MEETS CODE |
| | REQUIREMENTS NOR DO THEY REFLECT THE |
| | FLOOR PLAN. THE RISER DIAGRAM ON SHEET |
| | A8 DOES NOT REFLECT THE FLOOR PLAN |
| | BECAUSE THE DRINKING FOUNTAIN IS MISSING |
| | AND THE MOP SINK IS SHOWN ON THE SAME |
| | SIDE OF THE ROOM AS THE W/C. THE LAV IS |
| | NOT VENTED AS SHOWN. THE MOP SINK |
| | REQUIRES A TRAP. SHOW ALL PIPE SIZES. |
| | SECTIONS 104.2.1, 901.2.1, 1002.1- THE |
| | SANT. RISER DIAGRAM SUBMITTED ON AN |
| | 8-1/2" X 11" SHEET DOES NOT REFLECT THE |
| | FLOOR PLAN, THE MOP SINK, LAV, AND |
| | DRINKING FOUNTAIN ARE NOT VENTED. |
| | HORIZONTAL DRY VENTS ARE PROHIBITED. THE |
| | W/C SHALL NOT BE DOUBLE TRAPPED. THE W/C |
| | HAS AN INTEGRAL TRAP. SECTIONS 104.2.1, |
| | 1002.1., 901.2.1, 905.3, 905.4. - THE |
| | TITLE BLOCK FOR THE ENGINEER CAN NOT BE |
| | READ. FAC 61G15-23.002(2) & FS 471.2055 |
| | - SUBMIT ONLY ONE SANT. RISER DIAGRAM |
| | THAT MEETS CODE REQUIREMENTS AND |
| | REFLECTS THE FLOOR PLAN. SECTION |
| | 104.3.1.1. |
| | ***NO WATER RISER DIAGRAM HAS BEEN |
| | SUBMITTED. - SANITARY RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN, NOR DOES IT |
| | MEET CODE REQUIREMENTS. ONLY THE |
| | FIXTURES WITHIN THE BATHROOM GROUPS |
| | SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF |
| | THE BATHROOM GROUP. (SEE RED-LINED |
| | EXAMPLE OF A SANT. RISER DIAGRAM THAT |
| | REFLECTS THE FLOOR PLAN AND MEETS CODE |
| | REQUIREMENTS. |
| | |
| | 6. SHT A8 HC LAV DETAILS 1 & 2 SUBMIT |
| | DETAILS FOR THE FOLLOWING: |
| | FOR THE W/C: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE - NOT |
| | SHOWN. |
| | FOR THE LAV: |
| | F. 11-4.19.5 FAUCETS - NOT SHOWN PER |
| | CODE SECTION. |
| | FOR THE DRINKING FOUNTAIN. |
| | G. 11-4.15.2 SPOUT HEIGHT |
| | H. 11-4.15.3 SPOUT LOCATION |
| | I. 11-4.15.4 CONTROLS |
| | J. 11-4.15.5 CLEARANCES & CLEAR FLOOR |
| | SPACE. |
| | K. 11-4.1.3(10)(A) FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. - NO |
| | DETAIL FOR THE DRINKING FOUNTAIN |
| | SUBMITTED. |
| | ***THE ABOVE ACCESSIBLE REQUIREMENTS ARE |
| | NOT SHOWN ON THE PLANS AS REQUESTED. |
| | |
| | 7. SHT A1 IN THE REMOVAL OF ANY PART OF |
| | A DRAINAGE SYSTEM, DEAD ENDS ARE |
| | PROHIBITED. (INFORMATIONAL) - ALL |
| | CAPPED PIPES FOR DEMO SHALL BE INSPECTED |
| | BY THE FIELD INSPECTOR PRIOR TO |
| | COVERING. SECTION 704.5 - INDICATE ON |
| | THE DEMO SHEET WITH A NOTE. |
| | ***THE ABOVE INFORMATION IS NOT SHOWN ON |
| | THE PLANS AS REQUESTED. |
| | |
| | **************NEW COMMENT************** |
| | |
| | 1B. THE ADDRESS REQUIRED IN THE TITLE |
| | BLOCK OF THE ENGINEER DOES NOT REFLECT |
| | THE ADDRESS OF RECORD ON THE DBPR WEB |
| | SITE. PLEASE CORRELATE THE INFORMATION |
| | IN THE TITLE BLOCK TO REFLECT THE DBPR |
| | WEB SITE. FAC 61G15-23.002(2) AND FS |
| | 471.025. (SEE ATTACHED SHEET FROM DBPR) |
| | |
| | 2B. SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL AND FS 553.80(2)(B). |
| | THIS IS GIVEN AS A NOTICE. IF COMMENTS |
| | ARE NOT ADDRESSED AFTER THE THIRD |
| | REVIEW, 4 TIMES THE PLAN REVIEW PORTION |
| | WILL BE ACCESSED TO THE DESIGN |
| | PROFESSIONAL. |
| | |