Plan Review Notes
Plan Review Notes For Permit 05060920
Permit Number 05060920
Review Stop E
Sequence Number 3
Notes
Date Text
2006-05-31 00:00:00NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. THE RATING
 INDICATED ON THE GEAR (WHICH IS NOT A
 STANDARD RATING)IS THE SAME AVAILABLE AT
 THE TRANSFORMER.
  
 2} THE DISCONNECT ON THE RISER IS NOT ON
 THE PLAN AS NOTED IN THE LAST REVIEW.
  
 3} THE EQUIPMENT GROUND FROM THE METER
 TO THE DISCONNECT MUST BE REMOVED TO
 PREVANT OBJECTIONAL CURRENT. SEE 250.6.
  
 4} SEE PREVIOUS NOTE #4. SUBMIT ALL
 DETAILS AND SPECIFICATIONS FOR THE FIRE
 PUMP AND CONTROLLER. ALSO SHOW THE FEED
 TO SAME ON THE RISER. THERE IS NO RECORD
 OF THE PUMP OR CONTROLLER EVER BEING
 PERMITTED.
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW