| Plan Review Notes For Permit 05060920 |
| Permit Number |
05060920 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-05-31 00:00:00 | NONCOMPLIANT | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. THE RATING | | | INDICATED ON THE GEAR (WHICH IS NOT A | | | STANDARD RATING)IS THE SAME AVAILABLE AT | | | THE TRANSFORMER. | | | | | | 2} THE DISCONNECT ON THE RISER IS NOT ON | | | THE PLAN AS NOTED IN THE LAST REVIEW. | | | | | | 3} THE EQUIPMENT GROUND FROM THE METER | | | TO THE DISCONNECT MUST BE REMOVED TO | | | PREVANT OBJECTIONAL CURRENT. SEE 250.6. | | | | | | 4} SEE PREVIOUS NOTE #4. SUBMIT ALL | | | DETAILS AND SPECIFICATIONS FOR THE FIRE | | | PUMP AND CONTROLLER. ALSO SHOW THE FEED | | | TO SAME ON THE RISER. THERE IS NO RECORD | | | OF THE PUMP OR CONTROLLER EVER BEING | | | PERMITTED. | | | | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | |
|