2006-06-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS OUTSTANDING FROM PREVIOUS
 REVIEWS, NUMBERING REMAINING THE SAME
 FOR CONSITENCY:
  
 4.)PROVIDE A SUREVY OF THIS PROPERTY
 SO THAT FBC TABLE 600 COMPLIANCE CAN BE
 DETERMINED. (1ST AND 2ND REVIEWS)
  
 3RD REVIEW - ONE HAS BEEN PROVIDED, BUT
 CONFLICTS WITH THE ARCHITECTURAL PLAN.
 EXPLAIN WHY A SIGNED, SEALED SURVEY
 SHOWS A DISTANCE FROM THE PROPERTY LINE
 OF 3.4' IN THE REAR, BUT THE SITE PLAN
 PREPARED BY A.GARGUILIO, PE SHOWS THE
 BUILDING AS LESS THAN 3' FROM THE
 PROPERTY LINE, REQUIRING 0 OPENINGS.
 THIS ISSUE SHOULD HAVE BEEN ADDRESSED
 PRIOR TO RESUBMITTAL.CODE COMPLIANCE
 CANNOT BE DETERMINED DUE TO INCONSISTENT
 INFORMATION.
  
 SEE FBC TABLE 600.IF THE BUILDING IS
 LESS THAN 3', 3 HOUR WALL REQUIRED FOR
 TYPE V 1 HR PROTECTED, 2 HOUR FOR TYEP V
 UNPROTECTED.
  
 6.)YOU HAVE DECLARED TYPE IV
 CONSTRUCTION.SEE FBC606.YOU HAVE
 COMBUSTIBLE WALLS AND ROOF, SO THIS IS
 NOT A TYPE IV. (1ST AND 2ND REVIEW).
  
 3RD REVIEW - YOU HAVE NOW DECLARED A
 TYPE V, 1 HOUR PROTECTED.HOW ARE THE
 STRUCTURAL ELEMENTS PROTECTED FBC TABLE
 600?THE DETAILS PROVIDED ARE NOT
 COMPLIANT FOR A 1 HOUR PROTECTED
 BUILLDING.
  
 SEE ALSO COMMENT 4 ABOVE.CODE
 COMPLIANCE CANNOT BE DETERMINED DUE TO
 INSUFFICIENT/CONFLICTING INFORMATION ON
 THE PLAN.
  
 7.)C1 ALSO STATES THAT 1 HOUR
 PROETECTION REQUIRED.SHOW COMPLIANCE,
 EITHER BY ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709. (1ST & 2ND REVIEWS)
  
 3RD REVIEW - NOT ADDRESSED.
  
 8.)YOU DECLARE AN OCCUPANT LOAD OF 71.
 HOW HAVE YOU ARRIVED AT THIS NUMBER?
 (1ST REVIEW)
  
 2ND REVIEW - NOW THE OCCUPANCY IS SHOWN
 AS 5; 1500/300.THE BUILDING IS 11,131
 SF.SEE FBC1003.1, FBC TABLE 1003.1.
  
 3RD REVIEW - NOT PROPERLY ADDRESSED.
 OCCUPANCY IS NOW "ONE EMPLOYEE".IT IS
 UNCLEAR AS TO HOW AN 11K+ BUILDING CAN
 HAVE AN OCCUPANCY OF ONE.
  
 13.)PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 ROOF/WALL PANELS
 METAL DOOR
 LOUVERS
  
 2ND & 3RD REVIEWS - SUBMIT THE
 INSTALLATION INSTRUCTIONS FOR THE
 BENCHMARK DOORS (STATE PRODUCT APPROVAL
 SUBMITTED).
  
 PSUBMIT STATE PRODUCT APPROVALS FOR THE
 ROLLUP DOOR, SINGLE HUNG WINDOW AND
 FIXED WINDOW, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 3RD REVIEW - THE LOCAL PRODUCT APPROVAL
 APPLICATION IS INCOMPLETE.THERE IS NO
 QUALITY ASSURANCE ENTITY ON THE
 APPLICATION.THE LOCAL PRODUCT APPROVAL
 CANNOT BE ISSUED WITHOUT A QUALITY
 ASSURANCE PROGRAM, FAC9B72.UNTIL PROOF
 OF A PROGRAM IS PROVIDED, A REVIEW WILL
 NOT BE DONE ON THE APPLICATION.SEE THE
 VALIDATION CHECKLIST AND FAC9B72 AT
 WWW.FLORIDABUILDING.ORG, PRODUCT
 APPROVAL.***THE LOCAL PRODUCT APPROVAL
 APPLICATION MAY BE SUBMITTED PRIOR TO
 RESUBMITTAL OF THE PLANS***
  
 14.)SHOW THE ACCESSIBLE ROUTE,
 FBC11-4.1.3.IT APPEARS THAT THERE IS A
 STEP UP INTO THE BUILDING.SHOW
 ELEVATIONS. (1ST REVIEW)
  
 2ND REVIEW - NOT ADDRESSED.THE
 BUILDING ELEVATIONS STILL SHOW A STEP
 INTO THE MAIN ENTRANCE.PROVIDE
 FINISHED FLOOR ELEVATIONS.
  
 3RD REVIEW - NOT ADDRESSED.PLAN STILL
 SHOWS STEPS AT THE FRONT DOOR.THE
 ROLLUP DOORS ARE NOT COMPLIANT AS AN
 ACCESSIBLE ENTRY.
  
 15.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, FBC11-4.13.9.(1ST
 REVIEW).
  
 2ND & 3RD REVIEWS - NOT ADDRESSED.
  
 16.)ACCESSIBLE PARKING REQUIRED,
 FBC11-4.1.2(5)(A). (1ST & 2ND REVIEWS)
  
 3RD REVIEW - THIS WAS ADDED TO THE PLAN,
 BUT DOES NOT HAVE ALL DIMENSIONS,
 SIGNAGE, ACCESS AISLE.IS THE
 ACCESSIBLE ROUTE THROUGH THE SIDE DOOR?
 NO ELEVATION CHANGE INFORMATION PROVIDED
 AS REQUESTED.
  
  
 19.)SEE FBC1012.THE TWO OPENINGS IN
 THE FRONT OF THE BUILDING ARE NOT
 COMPLIANT WITH THE REQUIREMENTS FOR
 EGRESS DOORS.ADDRESS.
  
 3RD REVIEW - EXIT LIGHTS SHOWN AT THE
 ROLLUP DOORS.NOT PROPERLY ADDRESSED.
  
 20.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED ON THE NEXT
 REVIEW AS REQUIRED BY FLORIDA STATUTE.
  
 3RD REVIEW - 4X FEE AGAINST A. GARGUILO,
 PE APPLIED TO PERMIT.
  
 21.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, INCLUDING ALL OF THE
 SWING DOORS AND ALSO THE ROLLUP DOORS
 FOR THE STORAGE UNITS FBC11-4.13.9.
  
 3RD REVIEW - NOT ADDRESSED.
  
 NEW COMMENTS:
  
 22.)(PROVIDING MORE DETAIL IN REGARDS
 WHAT IS REQUIRED TO SHOW COMPLIANCE WITH
 ITEM 14.) PROVIDE HEIGHT FOR THE FLOOR
 MOUNTING CHANNEL AT THE DOOR, STORAGE
 UNITS.THERE IS TO BE AN ACCESSIBLE
 ROUTE INTO THE STORAGE UNITS,
 FBC11-4.1.1(1)(A), FBC11-4.1.2(2).THE
 FLOOR PLAN DOES NOT SHOW A MAN DOOR,
 ONLY A ROLLUP DOOR, BUT A7 SHOWS A SWING
 DOOR AND A ROLLUP DOOR.DOORS ARE TO
 COMPLY WITH FBC11-4.13.AS THE DOORS
 ARE NOT SHOWN ON THE FLOOR PLAN, AND THE
 DETAILS ON A7 DO NOT SHOW DOOR SWING
 INFORMATION, MANEUVERING CLEARANCE
 CANNOT BE DETERMINED.
  
 A SWING DOOR IS REQUIRED FOR EGRESS,
 FBC1027.2, FBC1012.1.2.
  
 23.)THE PLANS NOW STATE CODE SUMMARY
 2004, FORMERLY STATED FBC 2001.
 GOVERNING CODE AT THE TIME OF
 APPLICATION WAS FBC2001.TO CHANGE
 CODE, SUBMIT A NEW PERMIT APPLICATION
 AND THE PLANS WILL BE REVIEWED UNDER
 FBC2004.
  
 24.)THE ACCESSIBLE BATHROOM DOOR LACKS
 THE MANEUVERING CLEARANCE REQUIRED BY
 FBC11-4.13.6, FBC11 FIGURE 25.
  
 25.)HOW DOES THE GATE OPEN?SHOW
 REACH RANGE, FBC11-4.2.5, FBC1104.2.6.
  
 26.)CHANGES WERE NOT CLOUDED.THIS
 REQUIRED A COMPLETE NEW REVIEW.TO
 EXPEDITE PLAN REVIEW, CLOUD ALL CHANGES.
  
 27.)A SET OF THE PLANS HAS BEEN
 RETAINED.THEY WILL BE FORWARDED TO
 FBPE WITH A COMPLAINT.
  
 28.)DOORS ARE SHOWN ENCROACHING THE
 PROPERTY LINE, SEE FBC3203.
  
 29.)PROVIDE DIMENSIONS FOR THE AWNING,
 FBC3204.3.
  
 30.)THIS IS A 25-50% IMPROVEMENT AS
 PER ARCHITECT'S LETTER AND APPRAISAL,
 FBC3401.2.2.
  
 31.)DECLARE A SUBCLASSIFICATION,
 FBC312.2.
  
 32.)A2 NOW HAS REFERENCE TO SHUTTERS,
 ALSO SHOWS IMPACT.REMOVABLE SHUTTERS
 ON COMMERCIAL BUILDINGS ARE TO BE
 APPROVED BY THE BUILDING OFFICIAL.
 SUBMIT A PLAN FOR INSTALLATION, SEE
 ATTCHED IMPLEMENTATION STANDARD, ITEM
 13.