Plan Review Notes
Plan Review Notes For Permit 05060920
Permit Number 05060920
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-15 00:00:00****** UNSAT ********
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 ELECTRICAL DEVICES AND CORRELATE WITH
 THE PANEL SCHEDULE SUBMTTED. PLEASE SEE
 700.12E FOR EM/EXT LTS.
 PLEASE SEE EM/EXT LTS SHALL BE CIRCUITED
 TO THE LOCAL BRANCH CIRCUIT IN THE AREA
 WHICH LTS ARE LOCATED.
  
 2)NOTE: PLEASE SEE PLANS STILLINDICATE
 TWO METERS, HOWEVER ONLY ONE NEW ON
 RISER.
 PLEASE ALSO SEE NEW DISCONNECT NOW SHOWN
 ON RISER IS NOT SHOWN ON PLANS.?
 215.5
  
 3)NOTE: PLEASE SEE MAIN GRONDING
 ELECTRODE SYSTEM SHALL CONTAIN ALL AS
 SHOWN AT SUB-PANEL. CWP, GRND ROD AND
 ANY NEW FOOTER STEEL.
 250.50
 SUB PANEL IS NOT REQUIRED TO ALSO
 CONTAIN A GROUNDING ELECTRODE SYSTEM,
 HOWEVER IT MAY BE DONE.
 250.50
  
 4)NOTE: PLEASE CLARIFY PUMP SHOWN AT
 FIRE SPRINKLER ENTRANCE LOCATION. PLEASE
 VERIFY IF "FIRE PUMP", PLEASE SUBMIT ALL
 INFORMATION FOR FIRE PUMP CONTROLLER
 ETC.
 PLEASE CALL TO GO OVER INFORMATION
 NEEDED IF INDEED THIS IS A FIRE PUMP.
 NO OTHER PUMP INFORMATION COULD BE
 LOCATED ON PANEL SCHEDULE OR LOAD CALCS.
 215.5
  
 5)NOTE: PLEASE SEE OFFICE DOES NOT SEEM
 TO SHOW ANY RECEPTS? PLEASE VERIFY.
 PLEASE SEE OFFICE LT AND RECEPTS ARE
 INDICATED ON PANEL SCHEDULE?
 PLEASE ALSO SEE #14 AWG IS SHOWN ON THE
 20A BRANCH CIRCUIT. A MAX LOAD OF 1440W
 IS TO BE ON A 15A CIRCUIT.
 PLEAS ADJUST.240.4,310.16,215.5
  
 6)NOTE: PLEASE VERIFY #10 AWG SHOWN FOR
 SMOKE DETECTORS CIRCUIT?
 PLEASE ALSO CLARIFY THIS AS A FIRE ALARM
 PANEL IS BEING INSTALLED, WOULD NOTTHE
 SMOKE DETECTORS BE WIRED INTOFACP?
 PLEASE ALSO SEE THESE DEVICES COULD NOT
 BE LOCATED ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE KNOW THAT SOME OF THE
 ABOVE COMMENTS MAY AFFECT FIRE REVIEW.
  
  
 ** PLEASE SEE ELECTRICAL SHEET IS
 LABELED AS SHEET "L", AND "E" SHEET IS
 FOR FIRE SPRKLR PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]