| 2005-11-15 00:00:00 | ****** UNSAT ******** |
| | |
| | 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL |
| | ELECTRICAL DEVICES AND CORRELATE WITH |
| | THE PANEL SCHEDULE SUBMTTED. PLEASE SEE |
| | 700.12E FOR EM/EXT LTS. |
| | PLEASE SEE EM/EXT LTS SHALL BE CIRCUITED |
| | TO THE LOCAL BRANCH CIRCUIT IN THE AREA |
| | WHICH LTS ARE LOCATED. |
| | |
| | 2)NOTE: PLEASE SEE PLANS STILLINDICATE |
| | TWO METERS, HOWEVER ONLY ONE NEW ON |
| | RISER. |
| | PLEASE ALSO SEE NEW DISCONNECT NOW SHOWN |
| | ON RISER IS NOT SHOWN ON PLANS.? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE MAIN GRONDING |
| | ELECTRODE SYSTEM SHALL CONTAIN ALL AS |
| | SHOWN AT SUB-PANEL. CWP, GRND ROD AND |
| | ANY NEW FOOTER STEEL. |
| | 250.50 |
| | SUB PANEL IS NOT REQUIRED TO ALSO |
| | CONTAIN A GROUNDING ELECTRODE SYSTEM, |
| | HOWEVER IT MAY BE DONE. |
| | 250.50 |
| | |
| | 4)NOTE: PLEASE CLARIFY PUMP SHOWN AT |
| | FIRE SPRINKLER ENTRANCE LOCATION. PLEASE |
| | VERIFY IF "FIRE PUMP", PLEASE SUBMIT ALL |
| | INFORMATION FOR FIRE PUMP CONTROLLER |
| | ETC. |
| | PLEASE CALL TO GO OVER INFORMATION |
| | NEEDED IF INDEED THIS IS A FIRE PUMP. |
| | NO OTHER PUMP INFORMATION COULD BE |
| | LOCATED ON PANEL SCHEDULE OR LOAD CALCS. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE OFFICE DOES NOT SEEM |
| | TO SHOW ANY RECEPTS? PLEASE VERIFY. |
| | PLEASE SEE OFFICE LT AND RECEPTS ARE |
| | INDICATED ON PANEL SCHEDULE? |
| | PLEASE ALSO SEE #14 AWG IS SHOWN ON THE |
| | 20A BRANCH CIRCUIT. A MAX LOAD OF 1440W |
| | IS TO BE ON A 15A CIRCUIT. |
| | PLEAS ADJUST.240.4,310.16,215.5 |
| | |
| | 6)NOTE: PLEASE VERIFY #10 AWG SHOWN FOR |
| | SMOKE DETECTORS CIRCUIT? |
| | PLEASE ALSO CLARIFY THIS AS A FIRE ALARM |
| | PANEL IS BEING INSTALLED, WOULD NOTTHE |
| | SMOKE DETECTORS BE WIRED INTOFACP? |
| | PLEASE ALSO SEE THESE DEVICES COULD NOT |
| | BE LOCATED ON PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE KNOW THAT SOME OF THE |
| | ABOVE COMMENTS MAY AFFECT FIRE REVIEW. |
| | |
| | |
| | ** PLEASE SEE ELECTRICAL SHEET IS |
| | LABELED AS SHEET "L", AND "E" SHEET IS |
| | FOR FIRE SPRKLR PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |