Plan Review Notes
Plan Review Notes For Permit 05060920
Permit Number 05060920
Review Stop B
Sequence Number 2
Notes
Date Text
2006-06-01 00:00:00GAVE TO MICHELLE, TO GIVE TO JOHN ROACH
2005-11-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS REVIEW, NUMBERING
 REMAINING THE SAME FOR CONSISTENCY
  
 3.)THIS IS AN OVER 50% IMPROVEMENT AND
 THE REQUIREMENTS OF FBC3401.7.2.6 APPLY.
 SOME OF THE COMMENTS RELATE TO THIS CODE
 SECTION.
  
 4.)PROVIDE A SURVEY OF THIS PROPERTY
 SO THAT FBC TABLE 600 COMPLIANCE CAN BE
 DETERMINED.
  
 NOT ADDRESSED
  
 6.)YOU HAVE DECLARED TYPE IV
 CONSTRUCTION.SEE FBC606.YOU HAVE
 COMBUSTIBLE WALLS AND ROOF, SO THIS IS
 NOT A TYPE IV.
  
 NOT ADDRESSED
  
 7.)C1 ALSO STATES THAT 1 HOUR
 PROTECTION REQUIRED.SHOW COMPLIANCE,
 EITHER BY ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709.
  
 NOT ADDRESSED
  
 8.)YOU DECLARE AN OCCUPANT LOAD OF 71.
 HOW HAVE YOU ARRIVED AT THIS NUMBER?
  
 NOW THE OCCUPANCY IS SHOWN AS 5;
 1500/300.THE BUILDING IS 11,131 SF.
 SEE FBC1003.1, FBC TABLE 1003.1.
  
 12.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 SEE ITEM 13 BELOW.
  
 13.)PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 ROOF/WALL PANELS
 METAL DOOR
 LOUVERS
  
 SUBMIT THE INSTALLATION INSTRUCTIONS FOR
 THE BENCHMARK DOORS (STATE PRODUCT
 APPROVALS SUBMITTED)
  
 SUBMIT STATE PRODUCT APPROVALS FOR THE
 ROLLUP DOOR, SINGLE HUNG WINDOW AND
 FIXED WINDOW
  
 PRODUCT APPROVALS REQUIRED FOR THE ROOF
 AND WALL PANELS, NONE SUBMITTED
  
 14.)SHOW THE ACCESSIBLE ROUTE,
 FBC11-4.1.3.IT APPEARS THAT THERE IS A
 STEP UP INTO THE BUILDING.SHOW
 ELEVATIONS.
  
 NOT ADDRESSED.THE BUILDING ELEVATIONS
 STILL SHOW A STEP INTO THE MAIN
 ENTRANCE.PROVIDE FINISHED FLOOR
 ELEVATIONS.
  
 15.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, FBC11-4.13.9.
  
 NOT ADDRESSED.
  
 16.)ACCESSIBLE PARKING REQUIRED,
 FBC11-4.1.2(5)(A).
  
 NOT ADDRESSED.
  
 17.)A NOTE ON THE PLAN STATES THAT
 FLOOR RAFTERS WILL REMAIN, BUT
 PARTITIONS ON THE SECOND FLOOR WILL BE
 REMOVED.C1 STATES THAT THIS IS A TWO
 STORY BUILDING.WHERE IS THE SECOND
 FLOOR PLAN AND HOW DO YOU GET TO THE
 SECOND FLOOR?
  
 THE NOTE ON C1 NOW STATES THAT THIS IS A
 ONE STORY BUILDING, BUT A1 SHOWS A FRAME
 2ND STORY.
  
 18.)FBC*1804.1.7, FINISH GRADE SHALL
 BE SLOPED AWAY FROM THE FOUNDATION FOR
 DRAINAGE, SEE BB-A5.
  
 NOT ADDRESSED.
  
 NEW COMMENT:
  
 19.)SEE FBC1012.THE TWO OPENINGS IN
 THE FRONT OF THE BUILDING ARE NOT
 COMPLIANT WITH REQUIREMENTS FOR EGRESS
 DOORS.ADDRESS.
  
 20.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED ON THE NEXT
 REVIEW AS REQUIRED BY FLORIDA STATUTE.
  
 21.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, INCLUDING ALL OF THE
 SWING DOORS AND ALSO THE ROLLUP DOORS
 FOR THE STORAGE UNITS FBC11-4.13.9.
  
 A SET OF THE PLANS HAS BEEN RETAINED.