| 2006-06-01 00:00:00 | GAVE TO MICHELLE, TO GIVE TO JOHN ROACH |
| 2005-11-10 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | COMMENTS FROM PREVIOUS REVIEW, NUMBERING |
| | REMAINING THE SAME FOR CONSISTENCY |
| | |
| | 3.)THIS IS AN OVER 50% IMPROVEMENT AND |
| | THE REQUIREMENTS OF FBC3401.7.2.6 APPLY. |
| | SOME OF THE COMMENTS RELATE TO THIS CODE |
| | SECTION. |
| | |
| | 4.)PROVIDE A SURVEY OF THIS PROPERTY |
| | SO THAT FBC TABLE 600 COMPLIANCE CAN BE |
| | DETERMINED. |
| | |
| | NOT ADDRESSED |
| | |
| | 6.)YOU HAVE DECLARED TYPE IV |
| | CONSTRUCTION.SEE FBC606.YOU HAVE |
| | COMBUSTIBLE WALLS AND ROOF, SO THIS IS |
| | NOT A TYPE IV. |
| | |
| | NOT ADDRESSED |
| | |
| | 7.)C1 ALSO STATES THAT 1 HOUR |
| | PROTECTION REQUIRED.SHOW COMPLIANCE, |
| | EITHER BY ASSEMBLY OR CALCULATED FIRE |
| | RESISTANCE FBC709. |
| | |
| | NOT ADDRESSED |
| | |
| | 8.)YOU DECLARE AN OCCUPANT LOAD OF 71. |
| | HOW HAVE YOU ARRIVED AT THIS NUMBER? |
| | |
| | NOW THE OCCUPANCY IS SHOWN AS 5; |
| | 1500/300.THE BUILDING IS 11,131 SF. |
| | SEE FBC1003.1, FBC TABLE 1003.1. |
| | |
| | 12.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | SEE ITEM 13 BELOW. |
| | |
| | 13.)PRODUCT APPROVALS REQUIRED FOR THE |
| | FOLLOWING: |
| | ROOF/WALL PANELS |
| | METAL DOOR |
| | LOUVERS |
| | |
| | SUBMIT THE INSTALLATION INSTRUCTIONS FOR |
| | THE BENCHMARK DOORS (STATE PRODUCT |
| | APPROVALS SUBMITTED) |
| | |
| | SUBMIT STATE PRODUCT APPROVALS FOR THE |
| | ROLLUP DOOR, SINGLE HUNG WINDOW AND |
| | FIXED WINDOW |
| | |
| | PRODUCT APPROVALS REQUIRED FOR THE ROOF |
| | AND WALL PANELS, NONE SUBMITTED |
| | |
| | 14.)SHOW THE ACCESSIBLE ROUTE, |
| | FBC11-4.1.3.IT APPEARS THAT THERE IS A |
| | STEP UP INTO THE BUILDING.SHOW |
| | ELEVATIONS. |
| | |
| | NOT ADDRESSED.THE BUILDING ELEVATIONS |
| | STILL SHOW A STEP INTO THE MAIN |
| | ENTRANCE.PROVIDE FINISHED FLOOR |
| | ELEVATIONS. |
| | |
| | 15.)PROVIDE INFORMATION IN REGARDS TO |
| | THE DOOR HARDWARE, FBC11-4.13.9. |
| | |
| | NOT ADDRESSED. |
| | |
| | 16.)ACCESSIBLE PARKING REQUIRED, |
| | FBC11-4.1.2(5)(A). |
| | |
| | NOT ADDRESSED. |
| | |
| | 17.)A NOTE ON THE PLAN STATES THAT |
| | FLOOR RAFTERS WILL REMAIN, BUT |
| | PARTITIONS ON THE SECOND FLOOR WILL BE |
| | REMOVED.C1 STATES THAT THIS IS A TWO |
| | STORY BUILDING.WHERE IS THE SECOND |
| | FLOOR PLAN AND HOW DO YOU GET TO THE |
| | SECOND FLOOR? |
| | |
| | THE NOTE ON C1 NOW STATES THAT THIS IS A |
| | ONE STORY BUILDING, BUT A1 SHOWS A FRAME |
| | 2ND STORY. |
| | |
| | 18.)FBC*1804.1.7, FINISH GRADE SHALL |
| | BE SLOPED AWAY FROM THE FOUNDATION FOR |
| | DRAINAGE, SEE BB-A5. |
| | |
| | NOT ADDRESSED. |
| | |
| | NEW COMMENT: |
| | |
| | 19.)SEE FBC1012.THE TWO OPENINGS IN |
| | THE FRONT OF THE BUILDING ARE NOT |
| | COMPLIANT WITH REQUIREMENTS FOR EGRESS |
| | DOORS.ADDRESS. |
| | |
| | 20.)SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW FEE WILL BE CHARGED IF THE |
| | COMMENTS ARE NOT ADDRESSED ON THE NEXT |
| | REVIEW AS REQUIRED BY FLORIDA STATUTE. |
| | |
| | 21.)PROVIDE INFORMATION IN REGARDS TO |
| | THE DOOR HARDWARE, INCLUDING ALL OF THE |
| | SWING DOORS AND ALSO THE ROLLUP DOORS |
| | FOR THE STORAGE UNITS FBC11-4.13.9. |
| | |
| | A SET OF THE PLANS HAS BEEN RETAINED. |