Plan Review Notes
Plan Review Notes For Permit 05060920
Permit Number 05060920
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT C-1 INDICATES OCCUPANCY AS
 MERCANTILE, BUT FLOOR PLAN AND "STORAGE"
 ON THE FRONT OF THE BUILDING INDICATE
 THAT THE OCCUPANCY WILL BE STORAGE. -
 MINIMUM FACILITIES FOR PLUMBING FIXTURES
 WILL BE CALCULATED FOR STORAGE. TABLES
 1003.1 & 403.1.
 2. SHT C-1 UNDER MINIMUM NUMBER OF
 PLUMBING FIXTURES, SECTION 403.2
 EXCEPTION 2 IS REFERENCED. PLEASE
 INDICATE ON THE PLANS THE NUMBER OF
 EMPLOYEES EMPLOYED FOR RECORD.
 3. SHT C-1 MINIMUM FACILITIES REQUIRES A
 DRINKING FOUNTAIN AND A SERVICE SINK PER
 TABLE 403.1. SHT A2 FLOOR PLAN DOES NOT
 SHOW THE LOCATION OF THE DRINKING
 FOUNTAIN, NOR DOES IT SHOW THE LOCATION
 OF THE SERVICE SINK. PLEASE SHOW THE
 LOCATION OF THESE REQUIRED FIXTURES.
 4. SUBMIT A WATER AND A SANITARY RISER
 DIAGRAM IN ISOMETRIC FORM. THE WATER
 RISER DIAGRAM SHALL SHOW ALL PIPE SIZES,
 VALVES, AND, IF REQUIRED BY SECTION
 604.9, WATER HAMMER ARRESTORS. - THE
 SANT. RISER DIAGRAM SHALL SHOW ALL PIPE
 SIZES, VENTS, TRAPS AND POINT OF
 CONNECTION. SECTION 104.3.1.1.
 5. SHT A-2 NEW FLOOR PLAN STATES "SEE
 BATHROOM DETAIL ON SH A-4". NO BATHROOM
 DETAIL ON SHT A4. PLEASE CLARIFY.
 SECTION 104.2.1.
 6. SHT A8 HC LAV DETAILS 1 & 2
 MEASUREMENTS CAN NOT BE READ. SUBMIT
 DETAILS FOR THE FOLLOWING:
 FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT (SHOWN MIN.)
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 WATER CLOSET TO BE 18" OFF WALL TO THE
 CENERLINE OF THE FIXTURE.
 FOR THE LAV:
 F. 11-4.19.5 FAUCETS
 LAV SHALL BE MINIMUM 15" OFF WALL TO THE
 CENTERLINE OF THE FIXTURE.
 FOR THE DRINKING FOUNTAIN.
 G. 11-4.15.2 SPOUT HEIGHT
 H. 11-4.15.3 SPOUT LOCATION
 I. 11-4.15.4 CONTROLS
 J. 11-4.15.5 CLEARANCES & CLEAR FLOOR
 SPACE.
 K. 11-4.1.3(10)(A) FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 7. SHT A1 IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITEDL. (INFORMATIONAL) - ALL
 CAPPED PIPES FOR DEMO SHALL BE INSPECTED
 BY THE FIELD INSPECTOR PRIOR TO
 COVERING. SECTION 704.5
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]