| Notes |
| Date |
Text |
| 2005-07-28 00:00:00 | ******DENIED****** | | | | | | 1) DRAWINGS SHOW AN ADDRESS ON THE | | | BUILDING THAT SHALL BE AT LEAST 6" IN | | | HEIGHT AND CONTRASTING TO THE | | | BACKGROUND. | | | | | | 2) PLEASE INDICATE WHAT CONTENTS WILL BE | | | STORED IN STORAGE AREAS. | | | | | | 3) PLEASE ILLUSTRATE THE TOTAL OCCUPANT | | | LOAD. DOORS SERVING AREAS WITH OCCUPANT | | | LOADS GREATER THAN 50 PERSONS SHALL | | | SWING IN THE DIRECTION OF TRAVEL. PLEASE | | | PROVIDE FURTHER INFORMATION REGARDING | | | SECURITY GATES. | | | | | | 4) PLEASE CLEARLY SHOW THE LOCATIONS OF | | | ALL ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTING. EMERGENCY LIGHTING IS REQUIRED | | | NFPA 101, SECTION 37.2.9. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 7) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 | | | | | | |
|