| 2005-07-01 00:00:00 | IN ELEC FOR REVIEW. |
| | ************ UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2)NOTE: PLEASE SHOW MIN CONDUCTORS FROM |
| | METER TO MAIN. 310.16/240.4,215.5 |
| | |
| | 3)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM MAIN TO PANEL. |
| | 250.110,250.24,250.122 |
| | |
| | 4)NOTE: PLEASE SEE NEW RE-LOCATED PANEL |
| | MAY NOT BE PLACED IN "STORAGE RM". |
| | PLEASE SEE 110.26, 408.16, ETC. |
| | |
| | 5)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULE. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE SEE LOAD CALCULATIONS SUBMITTED |
| | ARE RESIDENTIAL LOAD CALCS. |
| | |
| | 7)NOTE: PLEASE SEE PLANS SHOW TWO |
| | METERS?? |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/ VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |