| Date |
Text |
| 2005-08-08 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.THIS PROJECT INVOLVES A |
| | CHANGE OF OCCUPANCY.233-5025 |
| | |
| | 3.)THIS IS AN OVER 50% IMPROVEMENT AND |
| | THE REQUIREMENTS OF FBC3401.7.2.6 APPLY. |
| | SOME OF THE COMMENTS RELATE TO THIS CODE |
| | SECTION. |
| | |
| | 4.)PROVIDE A SURVEY OF THIS PROPERTY |
| | SO THAT FBC TABLE 600 COMPLIANCE CAN BE |
| | DETERMINED. |
| | |
| | 5.)MERCANTILE OCCUPANCY IS DECLARED ON |
| | C1, AS WELL AS SINGLE TENANT.IF THERE |
| | IS ONLY ONE TENANT, WHY ARE THERE |
| | MULTIPLE UNITS AND BAYS?PLEASE PROVIDE |
| | SOME INFORMATION IN REGARDS TO THE |
| | INTENDED USE OF THE BUILDING.FBC312, |
| | FBC310. |
| | |
| | 6.)YOU HAVE DECLARED TYPE IV |
| | CONSTRUCTION.SEE FBC606.YOU HAVE |
| | COMBUSTIBLE WALLS AND ROOF, SO THIS IS |
| | NOT A TYPE IV. |
| | |
| | 7.)C1 ALSO STATES THAT 1 HOUR |
| | PROTECTION REQUIRED.SHOW COMPLIANCE, |
| | EITHER BY ASSEMBLY OR CALCULATED FIRE |
| | RESISTANCE FBC709. |
| | |
| | 8.)YOU DECLARE AN OCCUPANT LOAD OF 71. |
| | HOW HAVE YOU ARRIVED AT THIS NUMBER? |
| | |
| | 9.)DETAILS A-A2, B-A2, AND C-A2 (SHOWN |
| | ON THE NEWFLOOR PLAN, A2) ARE NOT ON |
| | A2. |
| | |
| | 10.)INDICATE WHICH PRODUCTS YOU ARE |
| | INSTALLING ON THE PRODUCT APPROVALS. |
| | |
| | 11.)IMPACT PROTECTION REQUIRED, |
| | FBC1606.1.4.USE OF REMOVABLE SHUTTERS |
| | ON COMMERCIAL BUILDINGS REQUIRES |
| | APPROVAL FROM THE BUILDING OFFICIAL. |
| | SEE ATTACHED POLICY, ITEM #13.SUBMIT A |
| | PRE-STORM PREPARATION PLAN IF YOU WOULD |
| | LIKE TO REQUEST THE USE OF REMOVABLE |
| | SHUTTERS. |
| | |
| | 12.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 13.)PRODUCT APPROVALS REQUIRED FOR THE |
| | FOLLOWING: |
| | ROOF/WALL PANELS |
| | METAL DOOR |
| | LOUVERS |
| | |
| | 14.)SHOW THE ACCESSIBLE ROUTE, |
| | FBC11-4.1.3.IT APPEARS THAT THERE IS A |
| | STEP UP INTO THE BUILDING.SHOW |
| | ELEVATIONS. |
| | |
| | 15.)PROVIDE INFORMATION IN REGARDS TO |
| | THE DOOR HARDWARE, FBC11-4.13.9. |
| | |
| | 16.)ACCESSIBLE PARKING REQUIRED, |
| | FBC11-4.1.2(5)(A). |
| | |
| | 17.)A NOTE ON THE PLAN STATES THAT |
| | FLOOR RAFTERS WILL REMAIN, BUT |
| | PARTITIONS ON THE SECOND FLOOR WILL BE |
| | REMOVED.C1 STATES THAT THIS IS A TWO |
| | STORY BUILDING.WHERE IS THE SECOND |
| | FLOOR PLAN AND HOW DO YOU GET TO THE |
| | SECOND FLOOR? |
| | |
| | 18.)FBC*1804.1.7, FINISH GRADE SHALL |
| | BE SLOPED AWAY FROM THE FOUNDATION FOR |
| | DRAINAGE, SEE BB-A5. |
| | |