| Date |
Text |
| 2005-06-28 00:00:00 | DENIED; |
| | 1.PLEASE SUBMIT EQUIPMENT SPECIFICATIONS |
| | FROM MANUFACTOR. NFPA SEC 5.3.10.10.13.1 |
| | 2.SHOW RISER DIAGRAM FOR VACUUM, WATER |
| | AND AIR. SIZE ALL PIPE. |
| | 3.PLEASE ADD NOTE VACUUM PIPING MUST |
| | HAVE A 1/4" PITCH PER 10' OF PIPE, WITH |
| | CLEANOUTS AS REQUIRED BY SEC. |
| | 5.3.10.10.10.3. |
| | 4.VACUUM LINE CANNOT RUNIN CEILING TO |
| | SEERIZATION CENTER. (SEE NOT 3). |
| | 5.PROVIDE SPEC. SHEETS FOR STERILZER AND |
| | SHOW PLUMBING REQUIRED. NO PLUMBING |
| | REVIEW WAS DONE UNDER MASTER PERMIT # |
| | 05020807.PLESE SUBMIT PLUMBING PLANS FOR |
| | REVIEW. |
| | 6.VACUUM SOURCE SHALL BE DIRECTLY |
| | CONNECTED TO THE SANITARY DRAINAGE |
| | SYSTEM THRU A 2" TRAP 4" DEEP WITH A |
| | VENT. 5.3.3.6.3.1. |
| | 7. ADD NOTE SOLVENT-CEMENT JOINTS IN |
| | PLASTIC LEVEL 3 VACUUM PIPING SHALL BE |
| | ACCORDANCE WITH ASTM D 2855 PRESSURE |
| | FITTINGS ARE REQUIRED TO BE USED. |
| | 5.3.10.3.4. |
| | 8.THE QUALIFIER OF THE PLUMBING COMPANY |
| | MUST ALSO HOLD THE MEDICAL GAS |
| | QUALIFICATIONS. |
| | MED-GAS PLAN REVIEW BY; |
| | JOHN LEECH |
| | 805-6695 |
| | 9.ADDITIONAL FEES ARE PERMIT FEES ARE |
| | DUE FOR ADDITIONAL WORK TO BE DONE IE. |
| | WALLS ADDED, SINKAND DENTAL CHAIRS WERE |
| | NOT ON ARRIGNAL PLAN AND APPLICATION SUB |
| | MITED IN FEB. 2005. |