| 2005-06-27 00:00:00 | | | | INDICATE THE TRANSFER AWITCH BEING USED | | | AND SUBMIT A LOAD CALCULATION INDICATING | | | THE SWITCH IS ADEQUATE FOR THE LOAD TO | | | BE SERVED. | | | | | | SHOW THE PHYSICAL LOCATION OF ALL | | | SERVICE AND EMERGENCY ON A SITE PLAN SO | | | THAT SIGNAGE AND DISCONNECTING MEANS CAN | | | BE REVIEWED FOR COMPLIANCE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|