| Date |
Text |
| 2005-06-27 00:00:00 | ************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE ELECTRICAL SHEETS ARE |
| | TO BE SIGNED BY THE ENGINEER OF RECORD. |
| | INITIALS ARE NOT ACCEPTIBLE. |
| | FS 471.025 |
| | |
| | 2)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | CUT/SPEC SHEETS FOR ATS (S) TO BE |
| | INSTALLED. |
| | PLEASE SEE 225.36, THIS SHALL BE SERVICE |
| | ENT RATED. PLEASE SEE GEN IS NOT PART OF |
| | THIS PERMIT APPLICATION. PLEASE SEE |
| | GROUPING OF DISCONNECTING MEANS WILL BE |
| | REQUIRED WITH EXISTING MAINS ETC. |
| | 225.34 |
| | GEN IS TO BE SUBMITTED UNDER SEPARATE |
| | PERMIT IF NOT IN THIS SCOPE OF WORK. |
| | GEN WILL NOT BE PERMITTED AT LOCATION |
| | /FLR AS SHOWN ON PLANS FOR FUTURE |
| | PERMIT. |
| | |
| | 3)NOTE: PLEASE SEE ELECTRICAL ROOM DOES |
| | NOT SEEM TO SHGOW MIN CLEARENCE REQUIRED |
| | UNDER 110.26. |
| | |
| | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215.3,230.42, ETC. |
| | |
| | 5)NOTE: PLEASE SHOW GROUNDING FOR |
| | TRANSFORMER 250.30 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |