Plan Review Notes
Plan Review Notes For Permit 05060854
Permit Number 05060854
Review Stop G
Sequence Number 1
Notes
Date Text
2005-06-28 00:00:00PAUL SCHMITZ, PLUMBING & GAS
 PLANS EXAMINER
  
 561-805-6692
 [email protected]
 GAS PLAN
 REVIEW FBC 2001
  
 DENIED
  
 (1) THIS APPLICATION TO BE INCLUDED WITH
 AGEN-RES APPLICATION.
  
 (2) SUBMITT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS.
  
 (3) BTU LOAD ON SYSTEM REFERE TO TABLES
 402 (.1)
 THRU 402 (34)
  
 (4) INDICATE THE DELIVERY PSI, SEC
 402.2IF NATURAL GAS SPECIFY . 5 OR
 2PSI
 (5) END OF COMMENTS.